目 錄1. 安全注意事項(xiàng)·······················································································12. 安裝要求 ·····························································································12-1 安裝位置·························································································22-2 安裝方法·························································································32-3 電器配線························································································62-4 ... [收起]
[展開]
BD-3500THY頂裝博圖說明書
粉絲: {{bookData.followerCount}}
文本內(nèi)容
第1頁

蘇州博圖制冷設(shè)備有限公司

冊(cè)

BD-3500THY 工業(yè)機(jī)柜空調(diào)說明書

第2頁

目 錄

1. 安全注意事項(xiàng)·······················································································1

2. 安裝要求 ·····························································································1

2-1 安裝位置·························································································2

2-2 安裝方法·························································································3

2-3 電器配線························································································6

2-4 機(jī)器排水·························································································6

3. 啟動(dòng)與運(yùn)轉(zhuǎn)···························································································6

3-1 運(yùn)行前后注意事項(xiàng)···········································································6

3-2 機(jī)器操作說明··················································································7

4. 維護(hù)與保養(yǎng)·························································································10

4-1 定期清潔·······················································································10

4-2 長時(shí)間停用時(shí)注意··········································································10

5. 故障排除·····························································································10

附錄一······································································································11

附錄二······································································································11

第3頁

1. 安全注意事項(xiàng)

⑴ 當(dāng)用戶對(duì)本空調(diào)器進(jìn)行各種操作時(shí),請(qǐng)先詳讀本使用手冊(cè),并注意本手冊(cè)

中所提到的注意事項(xiàng),以避免出現(xiàn)意外情況;

⑵ 請(qǐng)勿用濕手操作,以免引起觸電;

⑶ 當(dāng)需要保養(yǎng)或維護(hù)時(shí),請(qǐng)先切斷所有電源以免引起觸電事故;

⑷ 空調(diào)器上不易放置任何物品,以免滑落造成人員傷害;

⑸ 當(dāng)機(jī)器在運(yùn)轉(zhuǎn)時(shí),請(qǐng)勿將手指或任何物品伸入進(jìn)、出風(fēng)口,以避免人員受

傷或機(jī)器損壞;

⑹ 本機(jī)器不宜露天放置以免雨水進(jìn)入機(jī)體內(nèi),并且也不適宜于安裝在振動(dòng)較

大或者移動(dòng)的設(shè)備上,當(dāng)客戶必需安裝在此種條件下時(shí),請(qǐng)務(wù)必致電本公司

咨詢;

⑺ 本空調(diào)器為工業(yè)用設(shè)備,當(dāng)須用于動(dòng)植物或食品等方面之特殊用途時(shí),請(qǐng)

致電本公司咨詢;

⑻ 禁止自行改裝、修理、拆卸或者移裝,欲進(jìn)行上述動(dòng)作前請(qǐng)先向?qū)I(yè)人員

咨詢,以防意外發(fā)生。

2. 安裝要求

本空調(diào)器為側(cè)掛式系列,側(cè)掛式(圖一),為使機(jī)組能在理想的狀況下工作,

在安裝上請(qǐng)注意以下要求:

圖一 側(cè)掛式

空調(diào)器

回風(fēng)

(熱)

出風(fēng)

(冷)

第4頁

2-1 安裝位置

⑴ 空調(diào)器需安裝在周圍空氣品質(zhì)良好的環(huán)境中,請(qǐng)勿放置于有腐蝕性氣體、

可燃性氣體、粉塵類氣體、油污類氣體等品質(zhì)較差的空氣中;如果確實(shí)需要

在粉塵及油污等品質(zhì)較差的環(huán)境中安裝空調(diào)器,則一定要每天做好空調(diào)器的

清潔和保養(yǎng)工作。

⑵ 空調(diào)器應(yīng)安裝在通風(fēng)良好且熱量易于排放的地方,因?yàn)榭照{(diào)器運(yùn)行時(shí)會(huì)

排出熱量,如果空調(diào)器周圍排氣不暢很容易導(dǎo)致其周圍的溫度升高,這將影

響空調(diào)器的制冷效果。見圖三,空調(diào)器進(jìn)、排風(fēng)口離墻面的間距應(yīng)大于

500mm;

⑶ 空調(diào)器周圍請(qǐng)勿放置雜物,以保持空氣暢通流通;

⑷ 本空調(diào)器不宜放置于陽光可以直射的地方,避免因陽光照射而吸熱,影

響冷卻效果。

⑸ 請(qǐng)安裝本空調(diào)器于周圍溫度在 45℃以下的范圍之內(nèi)高溫系列 65℃以下;

⑹ 本機(jī)安裝時(shí)請(qǐng)注意上下位置擺放正確,絕對(duì)不能倒置安裝,前后左右必

須保持垂直,其傾斜角不大于 5°如圖四所示;

⑺ 控制箱內(nèi)正對(duì)出風(fēng)口的電器元件與出風(fēng)口的最小距離應(yīng)大于 200mm,因

距離太近電器元件表面易產(chǎn)生水膜現(xiàn)象,從而導(dǎo)致電器故障的發(fā)生。若無法

避免,請(qǐng)?jiān)陔娖髟霸黾右粔K隔熱材料;并且箱內(nèi)出風(fēng)口四周的電器元件

與出風(fēng)口應(yīng)保持一定的距離,以便減小箱內(nèi)空氣的流通阻力。

⑻ 當(dāng)空調(diào)器工作時(shí),電控箱四周應(yīng)該密封,箱門盡量較少打開次數(shù),以便

箱體內(nèi)空氣的溫、濕度能控制在較為理想的狀態(tài)下。

圖三

第5頁

冷氣機(jī)

圖 四

錯(cuò) 誤 正 確 錯(cuò) 誤 正 確

2-2 安裝方法

⑴ 當(dāng)機(jī)組在搬運(yùn)、裝卸時(shí),請(qǐng)始終保持設(shè)備處于垂直直立狀態(tài),不要將設(shè)

備長期放在露天場所;

⑵ 為使空調(diào)器的冷卻效果最佳,請(qǐng)將機(jī)組直接安裝在電氣柜的外壁上,請(qǐng)

勿采用風(fēng)管的形式進(jìn)行送風(fēng),如若確實(shí)需要采用風(fēng)管送風(fēng),請(qǐng)先咨詢本公司

技術(shù)工程師;

⑶ 空調(diào)器在安裝之前,請(qǐng)先確認(rèn)好安裝位置的強(qiáng)度是否能承載機(jī)組,以免

造成人員受傷及設(shè)備損壞,當(dāng)安裝在電氣柜門上時(shí),最好該扇箱門能固定不

動(dòng),當(dāng)需要打開時(shí)請(qǐng)先確認(rèn)好加在門上的重量不會(huì)使整個(gè)電氣柜傾倒;

⑷ 電氣柜上必須開孔,以便使冷風(fēng)能進(jìn)入電控箱內(nèi),具體的開口尺寸請(qǐng)參

見圖五;

⑸ 箱體開孔時(shí)請(qǐng)嚴(yán)格參照開口尺寸進(jìn)行,孔口處的毛刺必須清除,以免劃

第6頁

傷機(jī)組;

⑹ 當(dāng)長期使用時(shí)請(qǐng)注意安裝螺栓是否損壞或脫落,若有而未加處理,將有

可能導(dǎo)致機(jī)器掉落而損壞;

⑺ 具體的安裝方式如下:

第7頁

C. 用升降車安全的把空調(diào)器從安裝面安

裝到電控箱上,注意安裝時(shí)把電線先從

電線孔伸入到電箱內(nèi),再在電控箱內(nèi)側(cè)

螺栓上墊好墊圈,并用螺帽擰緊。

d. 在機(jī)組底部出水口連接好排水管,

用抱箍固定好,另一端請(qǐng)引入排水溝

或蓄水桶內(nèi),檢測電源是否與機(jī)組匹

配,然后接上電源即可開機(jī)使用。

b. 卸下機(jī)組背后安裝螺釘上

的螺帽與墊圈,控制好螺栓

的伸出長度約 15mm

排水管

蓄水桶

螺帽與墊片

進(jìn)風(fēng)口

送風(fēng)口

a.首先在電控柜上開好與

所選空調(diào)相對(duì)應(yīng)的安裝孔

機(jī)柜開孔

電源線 機(jī)柜側(cè)面

或門

第8頁

2-3 電器配線:

⑴ 機(jī)組安裝好后請(qǐng)先檢查電源電壓值是否保持在容許額定值內(nèi),請(qǐng)避免電壓

值過高或過低,若所提供的電壓在額定值±10%以內(nèi),本機(jī)組可正常使用;

經(jīng)常在超過額定電壓值的環(huán)境中使用,將會(huì)大大縮短壓縮機(jī)和其他電氣設(shè)備

及元件的使用壽命,此類損壞不屬于我公司包修范圍,只負(fù)責(zé)收費(fèi)維

修。請(qǐng)用戶千萬注意.

⑵ 空調(diào)的電器箱在機(jī)體內(nèi)部,非專業(yè)維修人員請(qǐng)勿打開電器箱進(jìn)行操作。機(jī)

組引出一根電源線,當(dāng)安裝好后無需另外接線,將插頭插入電控箱內(nèi)的電源

插座即可;

⑶ 在機(jī)組的電器回路上請(qǐng)自行安裝斷路器或漏電保護(hù)裝置;

⑷ 請(qǐng)準(zhǔn)備本機(jī)專用電源插座,不要在同一個(gè)插座上使用過多電器裝置,否則

容易使電源超出負(fù)載,引發(fā)事故。

2-4 機(jī)器排水:(室外型底部無接管口,殼體會(huì)預(yù)留有漏水口)

本機(jī)器自身有除濕功能,當(dāng)機(jī)器運(yùn)行時(shí),它會(huì)慢慢除去電控箱內(nèi)空氣中的部

分水分,這部分水氣就會(huì)以液態(tài)的形式排出,排水管就起到排出這部分水的

作用,排水管的連接請(qǐng)注意以下幾點(diǎn):

⑴ 請(qǐng)先在機(jī)器排水口上連接好短接頭,然后把配給的軟管連接上,再用抱箍

緊固好連接處;

⑵ 根據(jù)實(shí)際情況排水軟管長度適當(dāng)即可,過長部分請(qǐng)切除;

⑶ 排水軟管請(qǐng)勿折彎、壓扁、阻塞或出口高于進(jìn)口,以免排水不暢,從而導(dǎo)

致機(jī)器內(nèi)產(chǎn)生淤水嚴(yán)重時(shí)產(chǎn)生外溢,引起空調(diào)器或者電氣柜故障。

3. 啟動(dòng)與運(yùn)行

3-1 運(yùn)行前后注意事項(xiàng)

⑴ 啟動(dòng)前請(qǐng)先檢查排水管是否已經(jīng)連接到位,電控箱門是否關(guān)嚴(yán),若均已到

位即可插上電源開始工作;

⑵ 當(dāng)在運(yùn)轉(zhuǎn)中需重新啟動(dòng)空調(diào)器時(shí),請(qǐng)間隔 3 分鐘以上,倘若頻繁啟動(dòng)且間

隔時(shí)間過短會(huì)引起機(jī)器損傷;

⑶ 當(dāng)空調(diào)器傾斜時(shí)請(qǐng)勿開啟,避免漏水、觸電等情況發(fā)生;

⑷ 空調(diào)器在出廠時(shí)溫度點(diǎn)已經(jīng)設(shè)定好為 30℃,若需重新設(shè)定時(shí)請(qǐng)控制在允

第9頁

許范圍之內(nèi)設(shè)定,以免引起機(jī)器運(yùn)行不正常;如果空調(diào)器有加熱功能,出廠

時(shí)設(shè)置為 5℃

⑸ 當(dāng)機(jī)器有異常噪音或異味(焦臭)等現(xiàn)象出現(xiàn)時(shí),請(qǐng)馬上關(guān)閉空調(diào)器,并

請(qǐng)專業(yè)人員進(jìn)行檢查維修。

3-2 機(jī)器操作說明

1,面板顯示操作:

·系統(tǒng)參數(shù)設(shè)置界面進(jìn)入:

使用一組密碼進(jìn)入?yún)?shù)設(shè)置狀態(tài)(出廠默認(rèn)密碼為 1111),按〖P〗鍵并保持 3 秒

鐘,數(shù)碼管顯示『---0』,按〖▼〗鍵循環(huán)選擇密碼當(dāng)前位,按〖▲〗鍵設(shè)置當(dāng)前

位密碼值, 密碼設(shè)置完成后按〖S〗鍵確認(rèn)。如果密碼錯(cuò)誤,顯示『Err』蜂鳴器

響三聲后退出參數(shù)設(shè)置狀態(tài);如果密碼輸入正確,蜂鳴器響一聲,進(jìn)入?yún)?shù)設(shè)置

狀態(tài),這時(shí)數(shù)碼管顯示『U10』,用〖▲〗或〖▼〗鍵選擇參數(shù)代碼,選定一個(gè)參

數(shù)后按〖S〗鍵顯示該參數(shù)的設(shè)定值,這時(shí)再按〖▲〗或〖▼〗鍵可對(duì)參數(shù)進(jìn)行

設(shè)置,設(shè)置完成后再按〖S〗鍵,回到顯示參數(shù)代碼狀態(tài)。

·系統(tǒng)參數(shù)設(shè)置界面退出:

當(dāng)參數(shù)設(shè)置完成后必須長按〖P〗鍵 3 秒, 系統(tǒng)退出參數(shù)設(shè)置狀態(tài),此次參數(shù)

設(shè)置被保存。在參數(shù)設(shè)置狀態(tài)如果連續(xù) 30 秒內(nèi)無按鍵操作,系統(tǒng)退出參數(shù)設(shè)置

狀態(tài),但此次參數(shù)設(shè)置無效,控制器仍按原來的參數(shù)運(yùn)行。

第10頁

序號(hào)

參數(shù)代

設(shè)置功能 設(shè)定范圍 說明

出廠設(shè)定

01 U00 制冷溫度設(shè)定 25~ 40℃ 30

02 U02 溫差 1.0~ 5.0℃ 5

03 U03 高溫報(bào)警溫度

-5.0~50℃ 高溫/低溫設(shè)定間隔 1℃

50

04 U04 低溫報(bào)警溫度 5

05 U05 蒸發(fā)風(fēng)機(jī)溫度設(shè)定 0~40℃ 26

06 U06 蒸發(fā)風(fēng)機(jī)溫差 1.0~ 5.0℃ 2

07 U10 溫控探頭校正

-3.0~+3.0

0

08 U11 蒸發(fā)器探頭校正

-3.0~+3.0

0

09 U12 高溫報(bào)警失效 0~1 0:禁用;1:啟用 1

10 U13 低溫報(bào)警失效 0~1 0:禁用;1:啟用 1

11 U14 系統(tǒng)缺氟失效 0~1 0:禁用;1:啟用 0

12 U21

蒸發(fā)器探頭使能設(shè)

0~1 0:禁用;1:啟用 0

13 U22 壓縮機(jī)工作模式 0~1

0:自動(dòng)模式(啟用壓縮

機(jī))

1:禁用模式

0

14 U24 風(fēng)機(jī)工作模式 0~1

0:溫控模式

1:常開模式

0

15 U26 外部輸入告警模式 0~1

0:常閉;

1:常開

1

16 U28 蜂鳴器報(bào)警 0~1 0:禁用;1:啟用 1

17 U29

壓縮機(jī)開機(jī)延時(shí)時(shí)

1~5 分鐘 3

18 U30

壓縮機(jī)最短持續(xù)運(yùn)

行時(shí)間

1~5 分鐘 3

19 U34 RS485 波特率設(shè)定 0~3

0:2400bps

1:4800bps

2:9600bps

3:19200bps

3

20 U35 設(shè)備地址 1~99 1

21 U99 密碼 0000 ~

9999

---- 1111

22 End 設(shè)定結(jié)束

第11頁

控制功能說明:

壓縮機(jī)控制

◇當(dāng)測量溫度 ≥【制冷設(shè)定溫度】 + 【溫差】,且壓縮機(jī)停機(jī)時(shí)間大于【壓縮

機(jī)開機(jī)延時(shí)時(shí)間】,壓縮機(jī)開啟;

◇當(dāng)測量溫度 ≤【設(shè)定溫度】,且壓縮機(jī)開機(jī)時(shí)間大于【壓縮機(jī)最短持續(xù)運(yùn)行時(shí)

間】,壓縮機(jī)關(guān)閉;

例如:【制冷設(shè)定溫度】為 25 度, 【溫差】為 2 度,則當(dāng)溫控傳感器檢測溫

度高于 27 度時(shí)啟動(dòng)壓縮機(jī),溫度

低于 25 度時(shí)關(guān)閉壓縮機(jī),將溫度控制在 25~27 度之間;

◇壓縮機(jī)強(qiáng)制啟動(dòng):

1.在壓縮機(jī)關(guān)閉情況下,按住〖▼〗鍵 5 秒不放,可以強(qiáng)制啟動(dòng)壓縮機(jī)。在壓

縮機(jī)強(qiáng)制啟動(dòng)狀態(tài)下,按住〖▼〗鍵 5

秒不放,可以取消強(qiáng)制啟動(dòng)壓縮機(jī),壓縮機(jī)恢復(fù)正常運(yùn)行。

2.壓縮機(jī)在強(qiáng)制啟動(dòng)狀態(tài)下持續(xù)運(yùn)行 60min 后,壓縮機(jī)恢復(fù)正常運(yùn)行。

壓縮機(jī)延時(shí)保護(hù)

◇運(yùn)行過程中壓縮機(jī)停機(jī),必須經(jīng)過【壓縮機(jī)開機(jī)延時(shí)時(shí)間】才能再次啟動(dòng);

◇運(yùn)行過程中壓縮機(jī)開啟,必須經(jīng)過【壓縮機(jī)最短持續(xù)運(yùn)行時(shí)間】才能以實(shí)際

情況停機(jī)(運(yùn)行最短時(shí)間為 3min);

風(fēng)機(jī)控制: 控制器在運(yùn)行過程中,風(fēng)機(jī)按照如下規(guī)則運(yùn)行:

如果風(fēng)機(jī)設(shè)定為常開,則送風(fēng)機(jī)始終開啟;

如果風(fēng)機(jī)設(shè)定為溫控則風(fēng)機(jī)根據(jù)溫控傳感器溫度進(jìn)行控制??刂茥l件如下:

◇當(dāng)測量溫度 ≥【蒸發(fā)風(fēng)機(jī)設(shè)定溫度】 + 【蒸發(fā)風(fēng)機(jī)溫差】,且風(fēng)機(jī)已經(jīng)停機(jī)

時(shí)間大于 1 分鐘,風(fēng)機(jī)開啟;

◇當(dāng)測量溫度 ≤【蒸發(fā)風(fēng)機(jī)設(shè)定溫度】,且風(fēng)機(jī)開機(jī)時(shí)間大于 1 分鐘,風(fēng)機(jī)關(guān)閉;

例如:【蒸發(fā)風(fēng)機(jī)設(shè)定溫度】為 23 度, 【蒸發(fā)風(fēng)機(jī)溫差】為 2 度,則當(dāng)溫控

傳感器檢測溫度高于 25 度時(shí)啟動(dòng)風(fēng)機(jī),溫度低于 23 度時(shí)關(guān)閉風(fēng)機(jī),將溫度控

制在 23~25 度之間;

4.維護(hù)與保養(yǎng)

請(qǐng)定期檢查排水管,并確定無堵塞現(xiàn)象,若排水不良易造成空調(diào)器漏水。請(qǐng)定期清洗空氣過

濾網(wǎng)和冷凝器。對(duì)于機(jī)器上安裝的是尼龍濾網(wǎng)的可直接從側(cè)面拔出

第12頁

4-1 定期清潔

本機(jī)的濾網(wǎng)材質(zhì)為尼龍濾網(wǎng),可直接從網(wǎng)罩上面拉出,用洗滌水清洗干凈,

并晾干后按原樣裝回,一般每周需清洗一次;

⑵ 請(qǐng)用中性清洗劑擦拭機(jī)體,避免使用硬刷及酸性清洗劑清洗,嚴(yán)禁用水沖

洗空調(diào)器,以防發(fā)生觸電事故;

4-2 長時(shí)間停用時(shí)注意

⑴ 請(qǐng)切斷電源,以防意外;

⑵ 清理冷凝器、過濾網(wǎng)及內(nèi)部油污;

⑶ 請(qǐng)對(duì)機(jī)器采取防塵措施,延長機(jī)器使用壽命。

4. 故障排除

故障狀況 1 電源接通后,室內(nèi)、室外風(fēng)機(jī)不運(yùn)轉(zhuǎn)

可能原因

※保險(xiǎn)絲熔斷

※停電或無電源

狀況排除

※更換保險(xiǎn)絲

※檢查電源狀況

故障狀況 2 在運(yùn)行中突然停機(jī),電控箱內(nèi)溫度高于設(shè)定點(diǎn)溫度兩度以上

可能原因

※環(huán)境溫度過高,導(dǎo)致壓縮機(jī)熱保護(hù)

※過濾網(wǎng)堵塞或者冷凝器過臟,導(dǎo)致壓縮機(jī)熱保護(hù)

狀況排除

※改善周邊環(huán)境,使散熱暢通

※對(duì)過濾器及冷凝器進(jìn)行清洗

故障狀況 3 機(jī)器正常運(yùn)轉(zhuǎn),卻不制冷

可能原因

※壓縮機(jī)損壞

※制冷系統(tǒng)泄露

※機(jī)組蒸發(fā)器大面積結(jié)霜

狀況排除

※更換壓縮機(jī),重新抽真空充注制冷劑

※查出泄露處,并重新抽真空加制冷劑

※立即停機(jī),把設(shè)定溫度調(diào)高到 35℃,十分鐘后重新開機(jī)

◇若上述措施均不能排除故障,請(qǐng)致電本公司咨詢!

附錄 1:產(chǎn)品技術(shù)參數(shù)

型號(hào):BD-3500THY 工作電源: 交流 220V ±10% 頻率 50Hz ±4%

運(yùn)行電流: <4.5A 功 率: 1570W

第13頁

制冷劑: R22 制冷量: 3500W

防護(hù)等級(jí):內(nèi)循環(huán):IP54 外循環(huán):IP34

允許機(jī)柜內(nèi)溫度設(shè)定范圍:25--38℃(出廠設(shè)定 30℃)

允許使用環(huán)境溫度范圍:-25--45℃

循環(huán)風(fēng)量: 內(nèi)循環(huán):650m 3/h 外循環(huán):1150m 3/h 噪音:70dB

附錄 2:電氣原理圖

室內(nèi)風(fēng)機(jī) 室外風(fēng)機(jī) 壓縮機(jī)

M1 M2 M3

C2 C3

L

N

PE

t℃溫控器

BD-3500THY主回路電路圖控制回路

第14頁

蘇 州 博 圖 制 冷 設(shè) 備 有 限 公 司

地址:蘇州市吳江區(qū)太湖新城鎮(zhèn)同安東路 60 號(hào)

電話:0512-63172851 0512-63172852

傳真:0512-63102853 郵編:215223

全國統(tǒng)一服務(wù)熱線: 400-920-7382

網(wǎng)址 www.botuzl.com Email:botu@botuzl.com

百萬用戶使用云展網(wǎng)進(jìn)行翻頁電子圖書制作,只要您有文檔,即可一鍵上傳,自動(dòng)生成鏈接和二維碼(獨(dú)立電子書),支持分享到微信和網(wǎng)站!
收藏
轉(zhuǎn)發(fā)
下載
免費(fèi)制作
其他案例
更多案例
免費(fèi)制作
x
{{item.desc}}
下載
{{item.title}}
{{toast}}