国产AV88|国产乱妇无码在线观看|国产影院精品在线观看十分钟福利|免费看橹橹网站

麥格米特低溫變頻機(jī)組(科萊泰克)

發(fā)布時(shí)間:2023-11-22 | 雜志分類(lèi):其他
免費(fèi)制作
更多內(nèi)容

麥格米特低溫變頻機(jī)組(科萊泰克)

建筑冷熱源一體化解決專(zhuān)家 第1頁(yè)/共24頁(yè)目 錄1、致用戶(hù)·························································································22、產(chǎn)品簡(jiǎn)介······················································································33、電氣控制及安裝·············································································44、機(jī)組安裝······················································································165、運(yùn)行調(diào)試······················································································186、故障代碼表及解決措施·... [收起]
[展開(kāi)]
麥格米特低溫變頻機(jī)組(科萊泰克)
粉絲: {{bookData.followerCount}}
文本內(nèi)容
第1頁(yè)

建筑冷熱源一體化解決專(zhuān)家 第1頁(yè)/共24頁(yè)

目 錄

1、致用戶(hù)·························································································2

2、產(chǎn)品簡(jiǎn)介······················································································3

3、電氣控制及安裝·············································································4

4、機(jī)組安裝······················································································16

5、運(yùn)行調(diào)試······················································································18

6、故障代碼表及解決措施····································································19

7、維護(hù)保養(yǎng)······················································································20

8、機(jī)組參數(shù)······················································································22

9、機(jī)組外形尺寸················································································23

10、熱泵基本原理 ··············································································24

警告

1. 機(jī)組拆箱后,請(qǐng)檢查制冷系統(tǒng)的壓力。如壓力低于 0.2Mpa,不得進(jìn)行后續(xù)的安裝工

作,請(qǐng)聯(lián)系經(jīng)銷(xiāo)商,檢查系統(tǒng)的氣密性。

2. 開(kāi)機(jī)前先核對(duì)銘牌內(nèi)電源規(guī)格與實(shí)際送電必須相符,并預(yù)熱 6 個(gè)小時(shí)后,才能開(kāi)機(jī)。

3. 主機(jī)出廠前已在本廠測(cè)試完畢,所以安全保護(hù)開(kāi)關(guān)均已設(shè)定妥當(dāng),用戶(hù)切勿自行調(diào)

整。

4. 檢修時(shí)請(qǐng)斷開(kāi)機(jī)組電源,不可帶電操作,以免機(jī)組啟動(dòng)造成人員傷亡。

5. 機(jī)組冬季停止運(yùn)行時(shí),機(jī)組絕對(duì)不能斷電,防止機(jī)組凍壞。

6. 冬季長(zhǎng)期停機(jī)時(shí)應(yīng)排放干凈系統(tǒng)里的水,以防止機(jī)組凍壞。

第2頁(yè)

佛山鎧耐空調(diào)設(shè)備有限公司

第2頁(yè)/共24頁(yè) 建筑冷熱源一體化解決專(zhuān)家

致 用 戶(hù)

1、 歡迎購(gòu)買(mǎi)科萊泰克熱泵機(jī)組產(chǎn)品,在安裝使用本設(shè)備之前,請(qǐng)閱讀本手冊(cè),閱讀后,請(qǐng)

妥善保管好本手冊(cè),以備以后參考。安裝和維修 需要熟悉國(guó)家和當(dāng)?shù)匕踩?guī)范的專(zhuān)業(yè)

人員承擔(dān)。如果在安裝維修及使用中未能遵守本手冊(cè)所包含的說(shuō)明和注意事項(xiàng)及安全規(guī)

范,可能會(huì)導(dǎo)致設(shè)備的損壞或財(cái)產(chǎn)損失,并且有可能造成操作人員的傷害。最好的預(yù)防

是正確的安裝、正確的操作和經(jīng)常性的維護(hù)與保養(yǎng)。

2、 由于科萊泰克將不斷改進(jìn)產(chǎn)品質(zhì)量及性能,保留未經(jīng)通知更改產(chǎn)品型號(hào)的權(quán)力,并不因

此承擔(dān)任何義務(wù)。

3、 在閱讀本手冊(cè)中,如果您需技術(shù)咨詢(xún),請(qǐng)您與科萊泰克公司或當(dāng)?shù)劁N(xiāo)售商聯(lián)系。

注意:一旦發(fā)生器具以外的接地系統(tǒng)異常情況時(shí),應(yīng)立即停止使用熱泵機(jī)組。并拔下其

電源插頭或斷開(kāi)與供電電路的一切連接,并與制造廠的維修人員聯(lián)系處理。

第3頁(yè)

佛山鎧耐空調(diào)設(shè)備有限公司

建筑冷熱源一體化解決專(zhuān)家 第3頁(yè)/共24頁(yè)

產(chǎn) 品 簡(jiǎn) 介

安全可靠

科萊泰克熱泵機(jī)組是使用電力但不利用電力加熱的熱水裝置。因?yàn)椴皇褂秒娏χ苯蛹訜幔?/p>

水電完全隔離,安全系數(shù)進(jìn)一步提高。它沒(méi)有電熱泵機(jī)組、燃?xì)鉄岜脵C(jī)組使用中存在的易觸

電、易燃、易爆、易中毒等安全問(wèn)題,是當(dāng)今較為安全的熱水供給設(shè)備。

高效省電

科萊泰克熱泵機(jī)組采用熱泵制熱,從空氣中獲得大量的免費(fèi)熱能,因此提供相同的熱水

量,用電量?jī)H僅是傳統(tǒng)電熱泵機(jī)組的四分之一左右,可為用戶(hù)省下大筆的用電費(fèi)用。

綠色環(huán)保

科萊泰克熱泵機(jī)組采用太陽(yáng)能、空氣熱能和電能三種干凈能源,沒(méi)有使用油、煤、氣等

礦物燃料所造成的環(huán)境污染。它在工作過(guò)程中沒(méi)有排放有害氣體,用戶(hù)即使在密閉的空間里

沐浴,也不用擔(dān)心人體健康方面的問(wèn)題。

全天候使用

熱泵機(jī)組不受陰、雨等惡劣天氣的影響,一天二十四小時(shí)能全天候使用,彌補(bǔ)了一般太

陽(yáng)能受天氣環(huán)境影響,不能保證一年三百六十五天隨時(shí)供應(yīng)熱水的缺點(diǎn)。且安裝有精確的水

溫控制系統(tǒng),保證在沐浴過(guò)程中有恒定水溫。

長(zhǎng)久耐用

科萊泰克熱泵機(jī)組使用的壓縮機(jī)、四通閥等主要零配件采用世界名廠生產(chǎn)的優(yōu)質(zhì)產(chǎn)品,

再加以合理完善的生產(chǎn)工藝、嚴(yán)格的質(zhì)檢手段,使機(jī)組的性能完全得到了可靠保證。且經(jīng)過(guò)

嚴(yán)謹(jǐn)?shù)臏y(cè)試,其使用壽命長(zhǎng)達(dá)十年以上,遠(yuǎn)高于其它類(lèi)型熱泵機(jī)組的使用壽命。

安裝簡(jiǎn)單

科萊泰克熱泵機(jī)組安裝簡(jiǎn)便,且不受環(huán)境限制,可安裝在樓頂、陽(yáng)臺(tái)、車(chē)庫(kù)、廚房、儲(chǔ)

物間、地下室等地方,不須專(zhuān)人看管,不須設(shè)置專(zhuān)用機(jī)房。

操作簡(jiǎn)便,智能化運(yùn)行安全可靠

智能化運(yùn)行,可根據(jù)負(fù)荷變化自動(dòng)調(diào)整投入運(yùn)行的機(jī)組數(shù)量,實(shí)現(xiàn)最佳節(jié)能運(yùn)行。完善

可靠的全自動(dòng)控制系統(tǒng),同時(shí)機(jī)組設(shè)計(jì)配有多種保護(hù)措施,并有自動(dòng)防凍、自動(dòng)除霜等多種

控制,使機(jī)組運(yùn)行安全可靠,操作更為簡(jiǎn)單。

應(yīng)用廣泛

熱泵機(jī)組可滿(mǎn)足普通家庭和工廠、學(xué)校、賓館、酒樓、醫(yī)院、美容院、洗衣店、洗浴中

心等單位的需求,為用戶(hù)提供源源不斷的生活、生產(chǎn)所需熱水。

第4頁(yè)

佛山鎧耐空調(diào)設(shè)備有限公司

第4頁(yè)/共24頁(yè) 建筑冷熱源一體化解決專(zhuān)家

電 氣 控 制 及 安 裝

一、操作面板

名稱(chēng) 符號(hào) 狀態(tài) 功能或含義

熱水符號(hào) 常亮 制熱狀態(tài)

化霜符號(hào) 常亮 化霜狀態(tài)

壓縮機(jī)符號(hào) 常亮 壓縮機(jī)運(yùn)行中

風(fēng)機(jī)符號(hào) 常亮 風(fēng)機(jī)運(yùn)行中

水泵符號(hào) 常亮 水泵運(yùn)行中

電輔熱符號(hào) 常亮 電輔熱運(yùn)行中(正常)

電輔熱符號(hào) 閃爍 電輔熱運(yùn)行中(速熱)

攝氏度符號(hào) 常亮 當(dāng)前顯示的是攝氏溫度

時(shí)間符號(hào) 常亮 顯示當(dāng)前的一個(gè)實(shí)時(shí)時(shí)間

定時(shí)時(shí)段 1 符號(hào) 常亮 設(shè)置定時(shí)時(shí)段 1 的時(shí)間

關(guān)機(jī)圖標(biāo)

制熱模式圖標(biāo)

時(shí)鐘/定時(shí)/功能顯示

鎖屏圖標(biāo)

化霜進(jìn)入圖標(biāo)

定時(shí)開(kāi)標(biāo)志

定時(shí)關(guān)標(biāo)志

溫度顯示圖標(biāo)

熱水模式

第5頁(yè)

佛山鎧耐空調(diào)設(shè)備有限公司

建筑冷熱源一體化解決專(zhuān)家 第5頁(yè)/共24頁(yè)

電 氣 控 制 及 安 裝

名稱(chēng) 符號(hào) 狀態(tài) 功能或含義

定時(shí)時(shí)段 2 符號(hào) 常亮 設(shè)置定時(shí)時(shí)段 2 的時(shí)間

定時(shí)符號(hào) 常亮 定時(shí)開(kāi)關(guān)機(jī)開(kāi)啟中

鎖鍵符號(hào) 常亮 當(dāng)前按鍵已鎖定

二、按鍵功能

序號(hào) 按鍵名稱(chēng) 圖標(biāo) 功能描述

1 開(kāi)關(guān)鍵

開(kāi)關(guān)機(jī);

2 功能鍵

模式切換

3 定時(shí)鍵

時(shí)鐘設(shè)置;定時(shí)開(kāi)關(guān)機(jī)設(shè)置

4 加鍵

水溫+或翻頁(yè)

5 減鍵

水溫-或翻頁(yè)

6 鎖定鍵 按鍵鎖定

7 組合鍵 “ ”+“ ” 強(qiáng)制“化霜”開(kāi)啟或關(guān)閉

1.1:開(kāi)關(guān)鍵

(1)在按鍵未鎖定狀態(tài)下,長(zhǎng)按此鍵 1 秒可以切換開(kāi)/關(guān)機(jī);

(2)在其他設(shè)置狀態(tài)下,按此鍵可返回主界面;并保存設(shè)置參數(shù)

1.2:功能鍵

(1)待機(jī)/開(kāi)機(jī)模式下,按上 鍵,進(jìn)入模式切換;

第6頁(yè)

佛山鎧耐空調(diào)設(shè)備有限公司

第6頁(yè)/共24頁(yè) 建筑冷熱源一體化解決專(zhuān)家

電 氣 控 制 及 安 裝

1.3 溫度增鍵和 溫度減鍵

(1) 、 翻頁(yè)查詢(xún)、修改參數(shù)值;

(2)結(jié)合功能鍵可對(duì)各參數(shù)進(jìn)行查詢(xún)和設(shè)置

(3)在各運(yùn)行模式中,按 鍵和 鍵可以直接調(diào)整當(dāng)前模式的設(shè)定溫度;

(4)在各模式下,顯示設(shè)定時(shí),“設(shè)置”+溫度點(diǎn)亮,關(guān)機(jī)后“設(shè)置”熄滅。

1.4 定時(shí)鍵

(1)實(shí)時(shí)時(shí)鐘設(shè)置狀態(tài)或定時(shí)功能設(shè)置;

1.5 鎖定鍵

長(zhǎng)按 1 秒 鍵屏幕鎖定,顯示“ ”,再長(zhǎng)按 1 秒屏幕解鎖。

2.功能

2.1 用戶(hù)參數(shù)查詢(xún)(開(kāi)關(guān)機(jī)均可查詢(xún))

在主界面下,長(zhǎng)按 鍵 5 秒進(jìn)入用戶(hù)參數(shù)查詢(xún)界面;進(jìn)入后按 鍵或 鍵可查

詢(xún)各個(gè)參數(shù);

在用戶(hù)參數(shù)查詢(xún)界面中,如連續(xù) 30 秒無(wú)按鍵操作,則自動(dòng)退出用戶(hù)參數(shù)查詢(xún),返回至主

界面;按 鍵也可以返回至主界面;

在用戶(hù)參數(shù)查詢(xún)界面中,C35~C39 存儲(chǔ) 5 個(gè)歷史故障代碼, C35 為最近的一次故障,按

故障出現(xiàn)的先后順序進(jìn)行存儲(chǔ),以此類(lèi)推。若沒(méi)有歷史故障代碼,則顯示“00”。

用戶(hù)參數(shù)查詢(xún)表

地址 狀態(tài)名稱(chēng) 單位 顯示范圍 備注(實(shí)測(cè)值*或者/)

C0 故障或保護(hù)代碼 按控制板故障表 故障代碼

C1 變頻壓縮機(jī)當(dāng)前實(shí)際頻率 Hz 0~99

C2 壓縮機(jī)相電流 A -9~99

C3 直流母線(xiàn)電壓 V -9~99 *10

C4 IPM 模塊溫度 ℃ -9~99

C5 AC 電壓 V -9~99 *10

C6 AC 電流 A -9~99

C7 當(dāng)前壓縮機(jī)運(yùn)行功率 W -9~99 *100

C8 外風(fēng)機(jī)轉(zhuǎn)速 RPM -9~99 *10

C9 當(dāng)前主路回氣目標(biāo)過(guò)熱度 ℃ 0~50

C10 當(dāng)前主路回氣實(shí)際過(guò)熱度 ℃ -9~99 注意是根據(jù)壓力傳感器計(jì)算值

第7頁(yè)

佛山鎧耐空調(diào)設(shè)備有限公司

建筑冷熱源一體化解決專(zhuān)家 第7頁(yè)/共24頁(yè)

電 氣 控 制 及 安 裝

C11 主路電子膨脹閥步數(shù) P -9~99 *10

C12 輔路電子膨脹閥步數(shù) P -9~99 *10

C13 高壓壓力值 -9~99 *100 (有壓力傳感器時(shí)有效)

C14 高壓飽和蒸發(fā)溫度 ℃ -9~99 (有壓力傳感器時(shí)有效)

C15 當(dāng)前排氣過(guò)熱度 ℃ -9~99 (有壓力傳感器時(shí)有效)

C16 主路低壓壓力 Kpa -9~99 *100(有壓力傳感器時(shí)有效)

C17 主路低壓飽和蒸發(fā)溫度 ℃ -9~99 (有壓力傳感器時(shí)有效)

C18 當(dāng)前輔路過(guò)熱度設(shè)置值 ℃ -9~99

C19 當(dāng)前輔路過(guò)熱度實(shí)際值 ℃ -9~99

C20 輔路低壓壓力值 Kpa -9~99 *100(有壓力傳感器時(shí)有效)

C21 輔路入口溫度值 ℃ -9~99 輔路低壓飽和蒸發(fā)溫度

C22 輔路出口溫度值 ℃ -9~99 EVI 回氣溫度

C23 排氣溫度值 ℃ -9~99

C24 室外盤(pán)管溫度 ℃ -9~99

C25 室外環(huán)境溫度 ℃ -9~99

C26 室內(nèi)環(huán)境溫度 ℃ -9~99

C27 室內(nèi)盤(pán)管溫度 ℃ -9~99

C28 進(jìn)水溫度 ℃ -9~99

C29 出水溫度 ℃ -9~99

C30 回氣溫度 ℃ -9~99

C31 歷史故障查詢(xún) 1

C32 歷史故障查詢(xún) 2

C33 歷史故障查詢(xún) 3

C34 歷史故障查詢(xún) 4 0

C35 歷史故障查詢(xún) 5 F2

C36 主控軟件校驗(yàn)碼 當(dāng)查詢(xún)校驗(yàn)碼時(shí)中間大雙 8

顯示 后4位校驗(yàn)碼

C37 主控 EE校驗(yàn)碼 當(dāng)查詢(xún)校驗(yàn)碼時(shí)中間大雙 8

顯示 后4位校驗(yàn)碼

C38 線(xiàn)控器校驗(yàn)碼 當(dāng)查詢(xún)校驗(yàn)碼時(shí)中間大雙 8

顯示 后4位校驗(yàn)碼

C39 驅(qū)動(dòng)軟件校驗(yàn)碼 當(dāng)查詢(xún)校驗(yàn)碼時(shí)中間大雙 8

顯示 后4位校驗(yàn)碼

C40 驅(qū)動(dòng) EE校驗(yàn)碼 當(dāng)查詢(xún)校驗(yàn)碼時(shí)中間大雙 8

顯示 后4位校驗(yàn)碼

C41 主控芯片廠家 RS瑞薩,ZW 中微

第8頁(yè)

佛山鎧耐空調(diào)設(shè)備有限公司

第8頁(yè)/共24頁(yè) 建筑冷熱源一體化解決專(zhuān)家

電 氣 控 制 及 安 裝

2.2 工廠參數(shù)查詢(xún)和設(shè)置(開(kāi)關(guān)機(jī)均可設(shè)定)

在主界面下,長(zhǎng)按 鍵 3 秒后,進(jìn)入工廠參數(shù)查詢(xún)界面;在工廠參數(shù)查詢(xún)界面中,按

上下鍵切換查詢(xún)參數(shù),短按功能鍵 進(jìn)入設(shè)置選擇序號(hào)的參數(shù)值界面,參數(shù)值閃爍顯示,

此時(shí)按 鍵或 鍵可修改當(dāng)前工廠參數(shù)值,設(shè)置完參數(shù)值后按 鍵確認(rèn)。

(1)按 鍵退回查詢(xún)狀態(tài);

(2)在用工廠數(shù)查詢(xún)或工廠參數(shù)設(shè)置界面中,如連續(xù) 30 秒無(wú)按鍵操作,則自動(dòng)退出工廠

參數(shù)查詢(xún)界面或工廠參數(shù)設(shè)置界面,返回至主界面;

(3)按 鍵也可以返回至主界面;

地址 狀態(tài)名稱(chēng) 單位 調(diào)整范圍 出廠

設(shè)置 備注

00 啟動(dòng)水溫回差 5 默認(rèn) 5℃

01 水泵運(yùn)行方式 0

00:水泵間隔運(yùn)行條件

控制(默認(rèn))

01:水泵隨壓縮機(jī)運(yùn)轉(zhuǎn)

控制

02:水泵一直運(yùn)行

02 水泵間隔運(yùn)行時(shí)間 min 5 默認(rèn) 5min

03 制熱主閥回氣目標(biāo)過(guò)熱度 ℃ 2

04 制冷主閥回氣目標(biāo)過(guò)熱度 ℃ 2

05 主路閥調(diào)節(jié)間隔時(shí)間 S 30

06 輔路閥目標(biāo)過(guò)熱度 ℃ 1

07 輔助電加熱進(jìn)入的外環(huán)條

默認(rèn)-20℃,EE

可改 -15

08 底盤(pán)加熱進(jìn)入外環(huán)溫度 ℃ -30~3℃ 0 默認(rèn) EE 值,可調(diào)

09 輔路調(diào)節(jié)時(shí)間 S 30~90S 60 默認(rèn) EE 值,可調(diào)

10 熱水模式 0~1 1 0 關(guān)閉;1 開(kāi)啟

11 風(fēng)機(jī)類(lèi)型選擇 0~3 0 默認(rèn) EE 值,可調(diào)

12 除霜條件 1 連續(xù)時(shí)間補(bǔ)償 min -30~50 0 默認(rèn) EE 值,可調(diào)

13 除霜條件 2 連續(xù)時(shí)間補(bǔ)償 min -30~50 0 默認(rèn) EE 值,可調(diào)

14 壓縮機(jī)強(qiáng)制運(yùn)行頻率 F 0~95HZ 0 備注說(shuō)明

15 主閥手動(dòng)調(diào)閥 P 0~480 0 備注說(shuō)明

16 輔閥手動(dòng)調(diào)閥 P 0~320 0 備注說(shuō)明

17 手動(dòng)調(diào)試模式 0~1 0

0 關(guān)閉;1 開(kāi)啟,備注

說(shuō)明

18 制熱設(shè)定溫度上限值 ℃ 40~60℃ 50

19 制熱設(shè)定溫度下限值 ℃ 20~40℃ 25

20 制冷設(shè)定溫度上限值 ℃ 15~25℃ 20

第9頁(yè)

佛山鎧耐空調(diào)設(shè)備有限公司

建筑冷熱源一體化解決專(zhuān)家 第9頁(yè)/共24頁(yè)

電 氣 控 制 及 安 裝

21 制冷設(shè)定溫度下限值 ℃ 7~15℃ 10

22 制冷主閥最小開(kāi)度 P 80~480 -

23 制熱主閥最小開(kāi)度 P 80~480 -

24 進(jìn)出水溫差過(guò)大保護(hù) ℃ 5~40 13 默認(rèn) EE 值,EE 可調(diào)

25 除霜退出外盤(pán)溫度 1 ℃ 12~22℃ 15 默認(rèn) EE 值,EE 可調(diào)

26 除霜退出外盤(pán)溫度 2 ℃ 4~11℃ 10 默認(rèn) EE 值,EE 可調(diào)

27 最長(zhǎng)除霜時(shí)間 min 6~16min 8 默認(rèn) EE 值,EE 可調(diào)

28 防液擊功能 0~1 3 0 關(guān)閉;1 開(kāi)啟

29 防液擊回氣過(guò)熱度指 0~5 5 EE 可調(diào)

00 地址說(shuō)明:默認(rèn)為 5℃(啟動(dòng)水溫回差)

制冷、制熱、熱水模式下設(shè)定只為該模式下的有效值

如制熱設(shè)定 10℃,熱水的依然是 5℃

01 地址說(shuō)明:默認(rèn)為 0(水泵運(yùn)行選擇)

0:跟隨壓縮機(jī)開(kāi)關(guān),達(dá)溫停機(jī)后隔(01 地址)min 開(kāi) 1min,關(guān)機(jī)延時(shí)(03 地址)min

關(guān)閉

1:跟隨壓縮機(jī)開(kāi)關(guān),關(guān)機(jī)延時(shí) 30s 關(guān)閉

2:跟隨線(xiàn)控器開(kāi)關(guān),除水流開(kāi)關(guān)保護(hù)停,其他保護(hù)不停,關(guān)機(jī)延時(shí) 30s 關(guān)閉

10 地址說(shuō)明:默認(rèn)為 0(熱水模式選擇)

0:關(guān)閉---如果 EE 選擇沒(méi)有熱水模式,線(xiàn)控選擇了 1 開(kāi)啟熱水模式,則可選擇 0 關(guān)閉

1:開(kāi)啟----如果 EE 選擇沒(méi)有熱水模式,則開(kāi)啟熱水模式

EE 參數(shù)選擇了熱水模式,則此設(shè)置沒(méi)有影響

11 地址說(shuō)明:默認(rèn)為 EE 值(風(fēng)機(jī)類(lèi)型選擇)

0:內(nèi)驅(qū)直流風(fēng)機(jī)

1:?jiǎn)螜n交流風(fēng)機(jī)

2:雙檔交流風(fēng)機(jī)

3:三擋交流風(fēng)機(jī)

14/15/16/17 地址說(shuō)明:(手動(dòng)設(shè)定參數(shù)運(yùn)行)

手動(dòng)調(diào)試-------需要線(xiàn)控器開(kāi)機(jī)壓縮機(jī)啟動(dòng)后再設(shè)定

14:頻率設(shè)定,建議不要設(shè)定低于 30HZ 的值作為長(zhǎng)時(shí)間運(yùn)行頻率

15:主閥開(kāi)度設(shè)定,建議設(shè)定值不要低于 40p

16:輔閥開(kāi)度設(shè)定,建議設(shè)定值不要低于 40p,設(shè)定為 0 則電磁閥關(guān)閉,不為 0,則電

磁閥開(kāi)啟

17: 默認(rèn)為 0,如設(shè)定為 1,則進(jìn)入手動(dòng)設(shè)定模式,無(wú)法再設(shè)為 0,想要恢復(fù)到正常調(diào)

節(jié),則需要線(xiàn)控關(guān)機(jī),自動(dòng)清除 14/15/16 的設(shè)定值,再線(xiàn)控開(kāi)機(jī) 3min 后正常運(yùn)行。

當(dāng)上述 14/15/16 地址的值設(shè)定好以后,再設(shè)定 17 地址,進(jìn)入手動(dòng)模式,否則頻率、

開(kāi)度都為 0

第10頁(yè)

佛山鎧耐空調(diào)設(shè)備有限公司

第10頁(yè)/共24頁(yè) 建筑冷熱源一體化解決專(zhuān)家

電 氣 控 制 及 安 裝

2.3 定時(shí)開(kāi)/關(guān)機(jī)時(shí)間設(shè)置(定時(shí)開(kāi)機(jī)只能在關(guān)機(jī)狀態(tài)下設(shè)置)

(1)在主界面上,按 鍵后可進(jìn)入定時(shí) 1 組的設(shè)置界面;

(2)進(jìn)入定時(shí) 1 組界面后,再按一下定時(shí)鍵,則代表定時(shí)開(kāi)機(jī)時(shí)間的小時(shí)部分的數(shù)字

閃爍,此時(shí)按上鍵或 鍵,則可對(duì)定時(shí) 1 組開(kāi)機(jī)的小時(shí)進(jìn)行設(shè)置;

(3)當(dāng)設(shè)置好定時(shí)開(kāi)機(jī)的小時(shí)部分后,再按一下定時(shí)鍵,則代表定時(shí)開(kāi)機(jī)時(shí)間的分鐘部分

的數(shù)字閃爍,此時(shí)按 鍵或 鍵,則可對(duì)定時(shí) 1 組開(kāi)機(jī)的分鐘進(jìn)行設(shè)置;

(4)當(dāng)設(shè)置好定時(shí) 1 組開(kāi)機(jī)的分鐘后,再按一下 鍵,則進(jìn)入定時(shí) 1 組關(guān)機(jī)的小時(shí)設(shè)置

設(shè)置方法同上;

(5)當(dāng)設(shè)置好定時(shí)關(guān)機(jī)時(shí)間后,再按一下 鍵,則確認(rèn)當(dāng)前設(shè)置定時(shí)開(kāi)關(guān)機(jī)時(shí)間,入定

時(shí) 2 組的開(kāi)/關(guān)機(jī)設(shè)置,設(shè)置與定時(shí) 1 組一致,并返回至主界面;

(6)在定時(shí)設(shè)置界面中,按一下 鍵,則可取消當(dāng)前時(shí)段的定時(shí)開(kāi)或關(guān);

(7)在定時(shí)界面中,如連續(xù) 30 秒無(wú)按鍵操作,則確認(rèn)當(dāng)前設(shè)置定時(shí)時(shí)間,返回至主界面

(8)在定時(shí)界面中,按一下 鍵,則確認(rèn)當(dāng)前設(shè)置定時(shí)時(shí)間,返回至主界面;

2.4 鎖定鍵及解鎖

(1)在 鍵狀態(tài)下,長(zhǎng)按 鍵 1 秒后,蜂鳴器“嘀”的響一聲后,解除鎖鍵;

(2) 連續(xù) 60 秒無(wú)操作時(shí),自動(dòng)加鎖,背光變暗,3 分鐘全滅。

2.5 強(qiáng)制除霜

(1)在開(kāi)機(jī)狀態(tài)下,同時(shí)長(zhǎng)按 鍵+ 鍵 5 秒進(jìn)入強(qiáng)制除霜;

(2)長(zhǎng)按 鍵+ 鍵 5 秒則退出強(qiáng)制除霜。

2.6 強(qiáng)制電加熱功能

開(kāi)機(jī)時(shí)同時(shí)長(zhǎng)按 鍵+ 鍵 3 秒開(kāi)啟/關(guān)閉手動(dòng)電加熱功能;

第11頁(yè)

佛山鎧耐空調(diào)設(shè)備有限公司

建筑冷熱源一體化解決專(zhuān)家 第11頁(yè)/共24頁(yè)

電 氣 控 制 及 安 裝

2.7 保護(hù)代碼查詢(xún)

長(zhǎng)按 鍵 10s 進(jìn)入查詢(xún)保護(hù)代碼界面:

若同時(shí)有多個(gè)保護(hù),輪流顯示

如沒(méi)有保護(hù),顯示- - - -

按 鍵,返回主界面

二、電氣安裝

現(xiàn)場(chǎng)需要安裝連線(xiàn)的線(xiàn)路有外接電源線(xiàn)、控制器線(xiàn)、機(jī)組連接線(xiàn)以及客戶(hù)配置水泵電源

線(xiàn)以及控制信號(hào)線(xiàn)。在機(jī)組安裝到位以后,即可連接電源線(xiàn)電器控制及安裝和連接線(xiàn),所有

導(dǎo)線(xiàn)必須連接牢固,并且不得與任何運(yùn)動(dòng)部件接觸。所有連接線(xiàn)必須采用橡膠線(xiàn)(要求采用

YZW-300/500、IEC57 號(hào)氯丁橡膠線(xiàn)),所有導(dǎo)線(xiàn)必須滿(mǎn)足本手冊(cè)要求。機(jī)組要求必須有接地

措施。所有的電器設(shè)備及其安裝工作都必須符合國(guó)家及當(dāng)?shù)匕踩?guī)范的要求,器具應(yīng)按照國(guó)

家布線(xiàn)規(guī)則進(jìn)行安裝。固定線(xiàn)路必須配有至少 3mm 觸點(diǎn)開(kāi)距的全極斷開(kāi)裝置。

序號(hào) 機(jī)型型號(hào) 電源 線(xiàn)徑規(guī)格(mm2

) 配置空氣開(kāi)關(guān)(A)

1 CAR-12 220V 2*6+1*2.5 32

2 CAR-20 220V 2*10+1*2.5 60

3 CAR-24 220V 2*10+1*2.5 60

4 CAR-32 220V 2*10+1*2.5 32

5 CAR-24 380V 3*4+2*2.5

6 CAR-32 380V 3*4+2*2.5 32

7 CAR-40 380V 3*4+2*2.5 32

8 CAR-60 380V 3*6+2*2.5 40

注:圖表所列為機(jī)組進(jìn)線(xiàn)總線(xiàn)線(xiàn)徑;地線(xiàn)應(yīng)長(zhǎng)于其他動(dòng)力線(xiàn),以防地線(xiàn)被拉斷。信號(hào)線(xiàn)與主電源線(xiàn)

必須分開(kāi)單獨(dú)布線(xiàn)。

第12頁(yè)

佛山鎧耐空調(diào)設(shè)備有限公司

第12頁(yè)/共24頁(yè) 建筑冷熱源一體化解決專(zhuān)家

電 氣 控 制 及 安 裝

A. 電路圖

L 電抗器

電路圖

第13頁(yè)

佛山鎧耐空調(diào)設(shè)備有限公司

建筑冷熱源一體化解決專(zhuān)家 第13頁(yè)/共24頁(yè)

電 氣 控 制 及 安 裝

B. 電路圖

濾波板

PE

R-IN S-IN T-IN N-IN R-OUT S-OUT T-OUT 24N-OUT

U V W壓縮機(jī)1 線(xiàn),水泵零線(xiàn)接端子排零線(xiàn)或電源零線(xiàn) 循環(huán)泵配置交流接觸器為三相電,如單相水泵請(qǐng)接任一相火 線(xiàn)短接,否則會(huì)造成短路使控制板損壞. 注意:循環(huán)泵與補(bǔ)水閥等輸出線(xiàn)為220V,絕對(duì)不能與零 虛線(xiàn)部分為客戶(hù)接線(xiàn)部分

L1 L2 L3

W V U

CN302 CN301

通訊口 與控制板 CN16

電抗器 L

+12V D2 C2 B2 A2

機(jī)

盤(pán)

內(nèi)

環(huán)

內(nèi)

護(hù)開(kāi)關(guān) 低壓保水流保護(hù)開(kāi)關(guān)

水泵 電加熱

M 交流風(fēng)機(jī)

PC監(jiān)控端口

+12V GND B A

+5V RX TX GND

+5V SWIM NRST GND

口主程序燒錄端

+5V SCL SDA GND EE燒錄端口

A B C D +12V A B C D +12V

主電子膨脹閥輔電子膨脹閥預(yù)留端口

端口與線(xiàn)控器通訊

+5V PS3 GND

4 3 2 1

ON 撥碼開(kāi)關(guān)

GND TXD RXD +5V

端口與驅(qū)動(dòng)板通訊

PWM GND FB A1 B1 GND +12V

預(yù)留端口

濟(jì)

經(jīng)

機(jī)

進(jìn)

內(nèi)

盤(pán)

回EVI

預(yù)留

預(yù)

Y/G

預(yù)

1 2 3 4 5

XT2

水泵

6

電加熱

7 8

N R

水流開(kāi)關(guān)

4 3 2 1

O N 撥碼開(kāi)關(guān)

9 10

T S

盤(pán)

高壓保護(hù)開(kāi)關(guān)

電路圖

第14頁(yè)

佛山鎧耐空調(diào)設(shè)備有限公司

第14頁(yè)/共24頁(yè) 建筑冷熱源一體化解決專(zhuān)家

電 氣 控 制 及 安 裝

電路圖

濾波板

PE

R-IN S-IN T-IN N-IN R-OUT S-OUT T-OUT N-OUT 24

U V 壓縮機(jī)

W

1 線(xiàn),水泵零線(xiàn)接端子排零線(xiàn)或電源零線(xiàn) 循環(huán)泵配置交流接觸器為三相電,如單相水泵請(qǐng)接任一相火 線(xiàn)短接,否則會(huì)造成短路使控制板損壞. 注意:循環(huán)泵與電加熱等輸出線(xiàn)為220 V,絕對(duì)不能與零 虛線(xiàn)部分為客戶(hù)接線(xiàn)部分

W V U

通訊 口 與控 制板

機(jī)

盤(pán)

內(nèi)

環(huán)

內(nèi)

護(hù)開(kāi) 關(guān) 低壓 保水流 保護(hù)開(kāi) 關(guān)

水泵電加熱

交流 風(fēng)機(jī)閥

PC監(jiān)控端口

口主程序燒錄端EE燒錄端口 主電子膨脹閥輔電子膨脹閥預(yù)留端口

端口與線(xiàn)控器通訊

撥碼開(kāi)關(guān)

端口與驅(qū)動(dòng)板通訊預(yù)留端口

濟(jì)

經(jīng)

機(jī)

進(jìn)

內(nèi)

盤(pán)

回EVI

預(yù)留

預(yù)

Y/G

預(yù)

1 2 3 4 5 XT2

水 泵 6

電加熱

7 8 N R

水流 開(kāi)關(guān)

水撥碼 開(kāi)關(guān)

9 10 T S

盤(pán)

高壓 保護(hù)開(kāi) 關(guān)

T S R

L 電抗器 DC +

DB+

DC +

PG ND

散熱 風(fēng)機(jī)

485通訊

殼頂 保護(hù)開(kāi) 關(guān)

1 2 3 4

W 1 V1 U1

風(fēng)機(jī)熱

電路圖

第15頁(yè)

佛山鎧耐空調(diào)設(shè)備有限公司

建筑冷熱源一體化解決專(zhuān)家 第15頁(yè)/共24頁(yè)

電 氣 控 制 及 安 裝

B.系統(tǒng)接線(xiàn)圖

配電柜(用戶(hù)自配)

動(dòng)

線(xiàn)

環(huán)

機(jī)

手操器連接線(xiàn)

控制線(xiàn) 控制線(xiàn)

水流開(kāi)關(guān)

動(dòng)

線(xiàn)

動(dòng)

線(xiàn)

圖 4 系統(tǒng)接線(xiàn)圖

說(shuō)明:配電柜為熱水系統(tǒng)總電源柜.用戶(hù)自配

動(dòng)力線(xiàn)為熱水系統(tǒng)主干電線(xiàn).用戶(hù)自配

控制線(xiàn)為系統(tǒng)各元件與主機(jī)的相關(guān)控制信號(hào)連接線(xiàn),用戶(hù)自配

手操器連接線(xiàn)為操作面板與主機(jī)之間的連接線(xiàn),隨機(jī)附件

固定線(xiàn)路必須配有至少 3mm 觸點(diǎn)開(kāi)距的全極斷開(kāi)裝置

第16頁(yè)

佛山鎧耐空調(diào)設(shè)備有限公司

第16頁(yè)/共24頁(yè) 建筑冷熱源一體化解決專(zhuān)家

機(jī) 組 安 裝

只有專(zhuān)業(yè)人員才能進(jìn)行機(jī)組的安裝與調(diào)試!

一、安裝準(zhǔn)備

驗(yàn)收

收到貨物時(shí)應(yīng)對(duì)機(jī)組進(jìn)行仔細(xì)檢查,以確認(rèn)運(yùn)輸過(guò)程中是否出現(xiàn)貨物破損現(xiàn)象,并按照

裝箱單清點(diǎn)主機(jī)及附件,

檢查

機(jī)組出廠前已充好氟利昂,安裝調(diào)試前注意檢查機(jī)組在運(yùn)輸搬運(yùn)過(guò)程中制冷劑有無(wú)泄漏。

搬運(yùn)

搬運(yùn)時(shí)應(yīng)使用叉車(chē)、起重機(jī)或吊索,將機(jī)組搬運(yùn)到指定地點(diǎn),搬運(yùn)時(shí)要采取減震措施,

防止碰撞、擦壞機(jī)組外部噴涂。機(jī)組應(yīng)保持垂直狀態(tài),嚴(yán)禁機(jī)組傾斜角度超過(guò) 30°。起吊時(shí),

吊繩不得碰風(fēng)機(jī)及網(wǎng)罩!吊裝時(shí)人員不可站于機(jī)器下方!

二、機(jī)組安裝

1、安裝位置

機(jī)組應(yīng)安裝在室外,且應(yīng)與鄰近墻面保持適當(dāng)距離,如圖 12 所示,以免阻止空氣流通影

響空調(diào)效果,同時(shí)也便于檢修。由于冷水機(jī)組具有一定的振動(dòng)及噪音,安裝時(shí)要求牢固、可

靠,底部應(yīng)稍微向后傾斜,但傾斜度不大于 5°,這樣有利于冷凝水的排除。

本機(jī)組可安裝于地面、屋頂、陽(yáng)臺(tái)或其它任何便于安裝并可承受機(jī)組運(yùn)行重量的地方。

707 400

地面 地面

400

>200

墻面

側(cè)面圖 正面圖

圖 6 機(jī)組室外安裝圖

警 告

第17頁(yè)

佛山鎧耐空調(diào)設(shè)備有限公司

建筑冷熱源一體化解決專(zhuān)家 第17頁(yè)/共24頁(yè)

機(jī) 組 安 裝

A、可能避免排風(fēng)方向面對(duì)常年強(qiáng)風(fēng)方向,保證排風(fēng)不會(huì)回流。

B、安裝位置要有足夠強(qiáng)度,機(jī)組底腳應(yīng)設(shè)減振器或減振墊,減少震動(dòng)傳遞。

C、應(yīng)避免安裝在臟物、落葉及昆蟲(chóng)聚集環(huán)境處,以防堵塞換熱器。

D、盡可能在機(jī)組上方安裝遮陽(yáng)棚,保護(hù)機(jī)組。

E、換熱器應(yīng)定期清掃,確保換熱效率。

F、機(jī)組應(yīng)安裝于離電源、水源較近的地方,以便于配線(xiàn)和補(bǔ)水。

G、機(jī)組不可使用還含有油、鹽、腐蝕性氣體的環(huán)境中,這些物質(zhì)會(huì)對(duì)、機(jī)組產(chǎn)生腐蝕,引

起故障甚至縮短機(jī)組壽命。

2、機(jī)組基礎(chǔ)

機(jī)組可直接用膨脹螺栓固定在機(jī)座上,機(jī)座安裝定位孔位置見(jiàn)機(jī)組外形圖所示,機(jī)座可

用水泥預(yù)制,預(yù)留排水溝。也可用槽鋼或工字鋼制作托架、加防震橡膠墊,置于地面或屋頂

平面。機(jī)座表面應(yīng)水平

三、水系統(tǒng)安裝

1、循環(huán)式熱水機(jī)組配管示意圖

單向閥

Y型過(guò)濾器

壓力膨脹罐3L

單向閥

Y型過(guò)濾器 自來(lái)水補(bǔ)水

電輔熱系統(tǒng)

電源控電加熱電源線(xiàn)4m

2 熱泵電源線(xiàn)6m

2

熱泵通訊線(xiàn)

制箱

防凍排水閥

總電源線(xiàn)10m2

接用戶(hù)電表

接室內(nèi)采暖供水管

接室內(nèi)采暖回水管

旁通閥

PPR-32

PPR-32

PPR-20

PPR-20

地面沖洗閥

水流開(kāi)關(guān)

截止閥

截止閥

循環(huán)水泵

截止閥

截止閥

圖7 循環(huán)式熱泵機(jī)組接管示意圖

注 意

第18頁(yè)

佛山鎧耐空調(diào)設(shè)備有限公司

第18頁(yè)/共24頁(yè) 建筑冷熱源一體化解決專(zhuān)家

機(jī) 組 安 裝

注 意: A、循環(huán)水系統(tǒng)配管完成后,于開(kāi)機(jī)前必須將水系統(tǒng)中空氣排盡;

B、水流開(kāi)關(guān)安裝在水平直管段,距彎頭、閥門(mén)等局部阻力件5倍以上管徑

C、為提高制冷(制熱)效果和節(jié)約能源,管道需保溫嚴(yán)密。

D、機(jī)組接管口必須安裝排水管以方便排盡機(jī)組內(nèi)水,防止凍結(jié)。

E、虛線(xiàn)框內(nèi)的配件為用戶(hù)自行配置。

F、在停電或者長(zhǎng)時(shí)間不開(kāi)機(jī)時(shí),必須將沖洗閥和排水閥打開(kāi),排干凈機(jī)組及管道中的水。

2、設(shè)計(jì)安裝

有關(guān)室內(nèi)機(jī)組及管道系統(tǒng)的設(shè)計(jì)安裝原則應(yīng)由專(zhuān)業(yè)人士并參照有關(guān)技術(shù)規(guī)范及技術(shù)要求

進(jìn)行,根據(jù)合適的屋型來(lái)設(shè)計(jì)管路走向,上圖只為客戶(hù)安裝提供一個(gè)參考。在安裝過(guò)程中,

要注意幾點(diǎn):

A、管道布置合理,如右圖所

示,應(yīng)采取如 A 管路走向而非 B 管路走

向, 盡量減少,彎曲、杜絕“U”形彎、“

門(mén)”形彎。避免“U”形彎、以免由此造

成排氣不暢,增大水阻,形成氣塞。

圖 8 水管示意圖

B、水管安裝應(yīng)垂直或水平,管路及連接部位均不得有漏水現(xiàn)象并保溫良好。應(yīng)在管

道的最高處設(shè)置排氣閥及補(bǔ)水膨脹水箱(開(kāi)式水箱)。

C、水平的管道走向要保持一定的坡度(3‰),以便順利將氣體排出。

D、冷水系統(tǒng)應(yīng)參考本說(shuō)明書(shū)所示方法配管,并按照水暖管道標(biāo)準(zhǔn)正確施工。

E、應(yīng)盡可能地減小水循環(huán)系統(tǒng)的阻力損失。

F、水系統(tǒng)與本機(jī)組進(jìn)出水連接口處及水系統(tǒng)的最低點(diǎn)均設(shè)置放水口,以便在長(zhǎng)時(shí)間停止

使用時(shí),從兩處放水口同時(shí)放出機(jī)組及系統(tǒng)內(nèi)的水,防止冬季水在換熱器、水泵及管道內(nèi)凍

結(jié),使機(jī)組損壞。

G、在進(jìn)水管中應(yīng)安裝水過(guò)濾器,安裝時(shí)注意流向,并在水過(guò)濾器兩端加裝截止閥,以

便拆卸清洗過(guò)濾器。

H、水系統(tǒng)配管完成后,應(yīng)進(jìn)行水壓試漏并排污,確保系統(tǒng)內(nèi)清潔,無(wú)銹渣污物,管路

方可與室外主機(jī)連接,以防污物進(jìn)入機(jī)組,使換熱器堵塞,造成機(jī)組損壞。

A

B

門(mén) 形 彎

U 形 彎

第19頁(yè)

佛山鎧耐空調(diào)設(shè)備有限公司

建筑冷熱源一體化解決專(zhuān)家 第19頁(yè)/共24頁(yè)

運(yùn) 行 調(diào) 試

一、運(yùn)行前準(zhǔn)備工作

1. 熱泵機(jī)組檢查

檢查機(jī)組外觀及機(jī)內(nèi)管路系統(tǒng)是否在安裝、運(yùn)輸過(guò)程中遭到損害。

檢查風(fēng)機(jī)扇葉是否與風(fēng)扇固定板和風(fēng)扇護(hù)網(wǎng)干涉。

檢查機(jī)組壓力表是否仍有壓力,確認(rèn)制冷劑是否泄漏。

2. 檢查配電系統(tǒng)

檢查所供電電源是否與本說(shuō)明書(shū)和機(jī)組銘牌上所要求的供電電源一致。

檢查所有供電和控制線(xiàn)路是否全部連接到位,是否按接線(xiàn)圖正確接線(xiàn),接地是否可靠,

所有接線(xiàn)端子是否全部緊固。確認(rèn)相序正確。

3. 檢查管路系統(tǒng)

檢查系統(tǒng)管路、補(bǔ)水管、回水管、壓力表、溫度計(jì)、閥門(mén)、水位開(kāi)關(guān)等設(shè)備是否安裝正

確。

檢查系統(tǒng)中應(yīng)該開(kāi)啟的閥門(mén)是否已全部開(kāi)啟,應(yīng)該關(guān)閉的閥門(mén)是否已全部關(guān)閉。

檢查機(jī)組水管內(nèi)是否存在空氣,若有,應(yīng)利用機(jī)內(nèi)水管上的手動(dòng)排氣閥和水泵上的排氣

閥,將機(jī)組管路內(nèi)的空氣排盡。

檢查系統(tǒng)的保溫措施是否良好。確保水系統(tǒng)過(guò)濾器無(wú)堵塞現(xiàn)象,使水路暢通無(wú)阻。確認(rèn)

水系統(tǒng)已經(jīng)清洗干凈

二、試運(yùn)行

機(jī)組運(yùn)行必須由專(zhuān)業(yè)人員操作!

當(dāng)對(duì)整個(gè)系統(tǒng)進(jìn)行全面檢查確認(rèn)符合要求后,可進(jìn)行整體試運(yùn)轉(zhuǎn),試運(yùn)轉(zhuǎn)前,壓縮機(jī)須預(yù)

熱 12 小時(shí)??蛇M(jìn)行整體試運(yùn)行。

接通電源,開(kāi)啟熱泵,主機(jī)延時(shí) 3 分鐘后自動(dòng)啟動(dòng)。對(duì)于三相電源機(jī)組,首先檢查風(fēng)扇、

水泵轉(zhuǎn)向是否正確,如轉(zhuǎn)向不對(duì)立即關(guān)閉電源,調(diào)整相序。

測(cè)量壓縮機(jī)運(yùn)轉(zhuǎn)電流,有無(wú)異常聲音。

觀察水溫變化以及機(jī)組的壓力變化有無(wú)異常。

檢查機(jī)組是否符合要求,運(yùn)行一段時(shí)間后,便可投入正常使用。

第20頁(yè)

佛山鎧耐空調(diào)設(shè)備有限公司

第20頁(yè)/共24頁(yè) 建筑冷熱源一體化解決專(zhuān)家

故 障 代 碼 表

線(xiàn)控器故障保護(hù)代碼顯示表

序號(hào) 故障原因

故障

代碼

進(jìn)入條件 解決措施

1 主板與驅(qū)動(dòng)板通訊故障 F0

數(shù)據(jù)線(xiàn)及連接問(wèn)題 檢查數(shù)據(jù)線(xiàn)并連接好

主板接收操作板失敗 換新的控制面板

2 線(xiàn)控器與主板通訊故障 F1

數(shù)據(jù)線(xiàn)及連接問(wèn)題 檢查數(shù)據(jù)線(xiàn)并連接好

主板接收操作板失敗 換新的控制面板

4 回水溫度傳感器損壞 E0

電路板上感溫探頭未插好或松動(dòng) 重新插好感溫探頭

感溫探頭損壞 更換相應(yīng)感溫探頭

5 出水溫度傳感器損壞 E1

電路板上感溫探頭未插好或松動(dòng) 重新插好感溫探頭

感溫探頭損壞 更換相應(yīng)感溫探頭

6

制冷蒸發(fā)盤(pán)管故障傳感

器故障 E2

電路板上感溫探頭未插好或松動(dòng) 重新插好感溫探頭

感溫探頭損壞 更換相應(yīng)感溫探頭

7

壓縮機(jī)回氣溫度傳感器

故障 E3

電路板上感溫探頭未插好或松動(dòng) 重新插好感溫探頭

感溫探頭損壞 更換相應(yīng)感溫探頭

8

室外盤(pán)管溫度傳感器故

E4

電路板上感溫探頭未插好或松動(dòng) 重新插好感溫探頭

感溫探頭損壞 更換相應(yīng)感溫探頭

9 環(huán)境溫度傳感器損壞 E5

電路板上感溫探頭未插好或松動(dòng) 重新插好感溫探頭

感溫探頭損壞 更換相應(yīng)感溫探頭

10 排氣溫度傳感器損壞 E6

電路板上感溫探頭未插好或松動(dòng) 重新插好感溫探頭

感溫探頭損壞 更換相應(yīng)感溫探頭

11

壓縮機(jī) EVI 回氣傳感器

故障 E7

電路板上感溫探頭未插好或松動(dòng) 重新插好感溫探頭

感溫探頭損壞 更換相應(yīng)感溫探頭

12

輔路低壓經(jīng)濟(jì)器進(jìn)口傳

感器故障 EA

電路板上感溫探頭未插好或松動(dòng) 重新插好感溫探頭

感溫探頭損壞 更換相應(yīng)感溫探頭

13 內(nèi)環(huán)境溫度傳感器故障 EB

電路板上感溫探頭未插好或松動(dòng) 重新插好感溫探頭

感溫探頭損壞 更換相應(yīng)感溫探頭

14

EVI 回路低壓傳感器故

EC

電路板上感溫探頭未插好或松動(dòng) 重新插好感溫探頭

感溫探頭損壞 更換相應(yīng)感溫探頭

15 壓機(jī)高壓故障 P7

膨脹閥開(kāi)度太小 調(diào)大膨脹閥過(guò)熱度

水流量過(guò)小

檢查水管路閥是否完全

打開(kāi),或更改水泵,加

大流量

換熱器結(jié)垢

機(jī)組運(yùn)行一段時(shí)間后會(huì)

產(chǎn)生結(jié)垢現(xiàn)象,清洗

第21頁(yè)

佛山鎧耐空調(diào)設(shè)備有限公司

建筑冷熱源一體化解決專(zhuān)家 第21頁(yè)/共24頁(yè)

故 障 代 碼 表

序號(hào) 故障原因

故障

代碼

進(jìn)入條件 解決措施

16 壓機(jī)低壓故障 P8

膨脹閥開(kāi)度太小 調(diào)大熱力膨脹閥開(kāi)度

系統(tǒng)有泄漏 檢漏并重新加注冷媒

翅片換熱器積塵 機(jī)組運(yùn)行一段時(shí)間后會(huì)產(chǎn)

生積塵現(xiàn)象,清洗

17 水流保護(hù) PC

水流開(kāi)關(guān)未正確接入電控箱內(nèi)

端子排 正確連接好

水流開(kāi)關(guān)的調(diào)節(jié)彈簧的預(yù)緊力

調(diào)整不正確,造成雖有足夠水

流量但水流開(kāi)關(guān)不閉合

調(diào)整水流開(kāi)關(guān)

水流開(kāi)關(guān)安裝不正確(方向錯(cuò)

誤,水流開(kāi)關(guān)的閥片選擇錯(cuò)誤) 重新安裝水流開(kāi)關(guān)

19 進(jìn)出水溫差過(guò)大保護(hù) H1

水流量偏小 調(diào)整水流量

系統(tǒng)有堵塞 清理水系統(tǒng)

水泵未運(yùn)行 檢查水泵

故障代碼 故障原因

F2 壓縮機(jī)啟動(dòng)異常(缺相、反轉(zhuǎn))

F3 壓縮機(jī)失步故障

F4 IPM 模塊故障

EE 主控板EE故障

EF 驅(qū)動(dòng)板EE故障

P1 室外機(jī) AC 電流保護(hù)停機(jī)

P2 壓縮機(jī)相電流保護(hù)停機(jī)

P3 室外機(jī) AC 電壓過(guò)高、過(guò)低保護(hù)

P4 直流母線(xiàn)電壓過(guò)高、過(guò)低保護(hù)

P5 IPM 溫度過(guò)高保護(hù)停機(jī)

P6 排氣溫度過(guò)熱保護(hù)停機(jī)

P9 制冷外盤(pán)管過(guò)熱保護(hù)停機(jī)

PH 制熱外環(huán)境溫度過(guò)高保護(hù)

PA 制冷內(nèi)盤(pán)防凍結(jié)保護(hù)停機(jī)

PB 制熱內(nèi)盤(pán)管過(guò)熱保護(hù)停機(jī)

PL 制冷外環(huán)境溫度過(guò)低保護(hù)

第22頁(yè)

佛山鎧耐空調(diào)設(shè)備有限公司

第22頁(yè)/共24頁(yè) 建筑冷熱源一體化解決專(zhuān)家

維 護(hù) 保 養(yǎng)

一、電氣

1、本機(jī)組應(yīng)配置專(zhuān)用電源,電源電壓波動(dòng)范圍為-10%至+10%,應(yīng)使用自動(dòng)空氣開(kāi)關(guān),其額定電

流為機(jī)組運(yùn)行電流的 1.5 倍,絕對(duì)禁止使用閘刀開(kāi)關(guān)。

注意:固定線(xiàn)路必須配有至少 3mm 觸點(diǎn)開(kāi)距的全極斷開(kāi)裝置

2、機(jī)組應(yīng)可靠接地,定期檢查機(jī)組的供電電源情況。

3、主機(jī)開(kāi)關(guān)切勿頻繁操作,每小時(shí)不應(yīng)超過(guò)四次。電控箱應(yīng)防止受潮。

4、經(jīng)常檢查機(jī)組的電源和電氣系統(tǒng)的接線(xiàn)是否牢固,電氣元件是否有動(dòng)作異常,如有應(yīng)及

時(shí)維修和更換。

5、機(jī)組安裝前,所需要設(shè)定的參數(shù),均已由公司設(shè)定完畢,一般情況下,不允許用戶(hù)自行

修改參數(shù),如果確實(shí)需要,請(qǐng)與代理商或本公司技術(shù)服務(wù)人員聯(lián)系。

二、機(jī)組

1、長(zhǎng)時(shí)停機(jī)以后再次開(kāi)機(jī)前,機(jī)組必須通電預(yù)熱 12 小時(shí)后才能開(kāi)機(jī),短時(shí)停機(jī)后機(jī)組不要

斷電,給壓縮機(jī)預(yù)熱,防止開(kāi)機(jī)損壞壓縮機(jī)。機(jī)組若長(zhǎng)期不使用,務(wù)必將機(jī)組與管路內(nèi)

存水排凈。機(jī)組冬季停止制熱運(yùn)行后,機(jī)組自動(dòng)執(zhí)行防凍功能,所以機(jī)組絕對(duì)不能斷電。

2、始終保持機(jī)組周?chē)辛己玫臒峤粨Q環(huán)境,熱交換器應(yīng)定期除塵。

3、應(yīng)設(shè)專(zhuān)人維修保養(yǎng),定期檢查機(jī)組運(yùn)行的壓力、溫度情況,檢查機(jī)組的管接頭及檢修閥頭

有無(wú)泄漏,并做好記錄。

三、水系統(tǒng)

1、系統(tǒng)內(nèi)之循環(huán)水應(yīng)保證水質(zhì)良好,應(yīng)定期檢查、清洗過(guò)濾器,以保證足夠的水流量,保證

機(jī)組的換熱效果。

2、水系統(tǒng)應(yīng)配用膨脹水箱(部分機(jī)組內(nèi)置),循環(huán)水應(yīng)保持清潔,如果當(dāng)?shù)厮|(zhì)不太好,應(yīng)

對(duì)補(bǔ)水進(jìn)行處理,方可進(jìn)入水系統(tǒng)中。系統(tǒng)內(nèi)最好使用軟水。

3、定期檢查系統(tǒng)補(bǔ)水及排氣裝置運(yùn)行是否正常,以免影響水循環(huán),從而影響機(jī)組的制冷、制

熱效果和機(jī)組的壽命。

4、若停機(jī)時(shí)間較長(zhǎng),應(yīng)將機(jī)組管路中的水放掉,并切斷電源,套好防護(hù)罩。再運(yùn)行時(shí),開(kāi)機(jī)

前對(duì)系統(tǒng)進(jìn)行全面檢查。

5、機(jī)組出現(xiàn)故障,用戶(hù)無(wú)法解決時(shí),請(qǐng)電告本公司在當(dāng)?shù)氐奶丶s維修部,以便及時(shí)派人維修。

第23頁(yè)

佛山鎧耐空調(diào)設(shè)備有限公司

建筑冷熱源一體化解決專(zhuān)家 第23頁(yè)/共24頁(yè)

維 護(hù) 保 養(yǎng)

6、主機(jī)冷凝器清洗,本公司建議采用 50℃-60℃、濃度為 15%的熱磷酸液清洗冷凝器,啟

動(dòng)主機(jī)自帶循環(huán)水泵清洗 3 小時(shí),最后用自來(lái)水沖洗 3 遍。(管道安裝時(shí)建議預(yù)留三通接

口,用絲堵封住一個(gè)接口),以備清洗時(shí)接管。禁止用腐蝕性的清洗液清洗冷凝器。

7、水箱需在使用一段時(shí)間后(一般為 12 個(gè)月,具體根據(jù)當(dāng)?shù)厮|(zhì)而定)需清除水垢。

8、常檢查水系統(tǒng)的補(bǔ)水、水箱的安全閥、液位控制器和排氣裝置工作是否正常,以免空氣進(jìn)

入系統(tǒng)造成水循環(huán)量減少,從而影響機(jī)組的制熱量和機(jī)組運(yùn)行的可靠性。檢查水泵,水路

閥門(mén)是否正常工作,水管路及水管接頭是否滲漏。

注意:一旦發(fā)生器具以外的接地系統(tǒng)異常情況時(shí),應(yīng)立即停止使用熱泵機(jī)組。并拔下其

電源插頭或斷開(kāi)與供電電路的一切連接,并與制造廠的維修人員聯(lián)系處理。

第24頁(yè)

滁州揚(yáng)子空氣源設(shè)備制造有限公司

建筑冷熱源一體化解決專(zhuān)家 第24頁(yè)/共24頁(yè)

熱 泵 基 本 原 理

一、熱泵機(jī)組的介紹

熱泵作為高效集熱并轉(zhuǎn)移熱能的裝置,可以把消耗的電力變?yōu)?3 倍甚至 3 倍以上的熱能,

實(shí)現(xiàn)低溫?zé)崮芟蚋邷責(zé)崮艿陌徇\(yùn),是當(dāng)今世界最經(jīng)濟(jì)最節(jié)能最安全,最環(huán)保的新一代熱水制造

設(shè)備。

二、熱泵機(jī)組及工作原理

在自然界中,水總由高處流向低處,熱量也總是從高溫傳向低溫。但人們可以用水泵把水

從低處提升到高處,從而實(shí)現(xiàn)水的由低處向高處流動(dòng),熱泵同樣可以把熱量從低溫傳遞到高溫。

所以熱泵實(shí)質(zhì)上是一種熱量提升裝置,熱泵的作用是從周?chē)h(huán)境中吸取熱量,并把它傳遞給被

加熱的對(duì)象(溫度較高的物體),其工作原理與制冷機(jī)相同,都是按照逆卡諾循環(huán)工作的,所

不同的只是工作溫度范圍不一樣。

如圖 12 所示,低環(huán)溫變頻空氣源熱泵機(jī)組,主要有翅片式蒸發(fā)器、壓縮機(jī)、水冷冷凝器

和膨脹閥四部分組成,通過(guò)讓工質(zhì)不斷完成蒸發(fā)(吸取蒸發(fā)器中的熱量)→壓縮→冷凝(放出

熱量)→節(jié)流→再蒸發(fā)的熱力循環(huán)過(guò)程,從而將低溫環(huán)境里的熱量轉(zhuǎn)移到水中,低環(huán)溫變頻空

氣源熱泵機(jī)組在工作時(shí),與普通的空調(diào)以及熱泵機(jī)組一樣 ,在蒸發(fā)器中吸收低溫環(huán)境介質(zhì)中

的能量 QA:它本身消耗一部分能量,即壓縮機(jī)耗電 QB:通過(guò)工質(zhì)循環(huán)系統(tǒng)在冷凝器中時(shí)行放熱

QC,QC=QA+QB,因此低環(huán)溫變頻空氣源熱泵機(jī)組的效率為(QB+ QC)/ QB ,而其他加熱設(shè)備

的加熱效率都小于 1,因此低環(huán)溫變頻空氣源熱泵機(jī)組加熱效率遠(yuǎn)大于其他加熱設(shè)備的效率,可

以看出,采用低環(huán)溫變頻空氣源熱泵機(jī)組作為加熱裝置可以節(jié)省能源,同時(shí)還降低 CO2 等污染

物的排放量,實(shí)現(xiàn)節(jié)能減排的效果。

進(jìn)水

出水

節(jié)流機(jī)構(gòu)

機(jī)

圖 12 低環(huán)溫變頻空氣源熱泵機(jī)組工作原理圖

百萬(wàn)用戶(hù)使用云展網(wǎng)進(jìn)行書(shū)冊(cè)翻頁(yè)效果制作,只要您有文檔,即可一鍵上傳,自動(dòng)生成鏈接和二維碼(獨(dú)立電子書(shū)),支持分享到微信和網(wǎng)站!
收藏
轉(zhuǎn)發(fā)
下載
免費(fèi)制作
其他案例
更多案例
免費(fèi)制作
x
{{item.desc}}
下載
{{item.title}}
{{toast}}