昆 山科諾泰電氣設備有限公司用戶操作使用說明書KBCW-600GR 工業(yè)柜空調(diào)說明書
昆 山科諾泰電氣設備有限公司用戶操作使用說明書KBCW-600GR 工業(yè)柜空調(diào)說明書
目錄1. 安全注意事項·······················································································1
2. 安裝要求 ·····························································································1
2-1 安裝位置·························································································2
2-2 安裝方法·························································································3
2-3 電器配線························································································6
2-4 機器排水·························································································6
3. 啟動與運轉···························································································6
3-1 運行前后注意事項···········································································6
3-2 機器操作說明··················································································7
4. 維護與保養(yǎng)·························································································10
4-1 定期清潔·······················································································10
4-2 長時間停用時注意··········································································10
5. 故障排除·····························································································10
附錄一······································································································11
附錄二······································································································11
1,安 全 注 意 事 項
⑴ 當用戶對本空調(diào)器進行各種操作時,請先詳讀本使用手冊,并注意本手冊中所提到的注意事項,以避免出現(xiàn)意外情況;
⑵ 請勿用濕手操作,以免引起觸電;
⑶ 當需要保養(yǎng)或維護時,請先切斷所有電源以免引起觸電事故;⑷ 空調(diào)器上不易放置任何物品,以免滑落造成人員傷害;
⑸ 當機器在運轉時,請勿將手指或任何物品伸入進、出風口,以避免人員受傷或機器損壞;
⑹ 本機器安裝結束后外罩連接部分請做防水處理,請按照我公司給出的正確安裝方式安裝。此空調(diào)不適宜于安裝在振動較大或者移動的設備上,當客戶必需安裝在此種條件下時,請務必致電本公司咨詢;
⑺ 本空調(diào)器為工業(yè)用設備,當須用于動植物或食品等方面之特殊用途時,請致電本公司咨詢;⑻ 禁止自行改裝、修理、拆卸或者移裝,欲進行上述動作前請先向?qū)I(yè)人員咨詢,以防意外發(fā)生。
1. 安裝要求
本空調(diào)器為側掛半嵌入式系列,嵌入式(圖一),為使機組能在理想的狀況下工作,在安裝上請注意以下要求:
圖一 側掛式
空調(diào)器
電
控
箱
回風
(熱)
出風
(冷)
2-1 安裝位置
⑴ 空調(diào)器需安裝在周圍空氣品質(zhì)良好的環(huán)境中,請勿放置于有腐蝕性氣體、可燃性氣體、粉塵類氣體、油污類氣體等品質(zhì)較差的空氣中;如果確實需要在粉塵及油污等品質(zhì)較差的環(huán)境中安裝空調(diào)器,則一定要每天做好空調(diào)器的清潔和保養(yǎng)工作。
⑵ 空調(diào)器應安裝在通風良好且熱量易于排放的地方,因為空調(diào)器運行時會排出熱量,如果空調(diào)器周圍排氣不暢很容易導致其周圍的溫度升高,這將影響空調(diào)器的制冷效果。見圖三,空調(diào)器進、排風口離墻面的間距應大于 500mm;
⑶ 空調(diào)器周圍請勿放置雜物,以保持空氣暢通流通;
⑷ 本空調(diào)器不宜放置于陽光可以直射的地方,避免因陽光照射而吸熱,影響冷卻效果。⑸ 請安裝本空調(diào)器于周圍溫度在 55℃以下的范圍之內(nèi)高溫系列55℃以下;⑹ 本機安裝時請注意上下位置擺放正確,絕對不能倒置安裝,前后左右必須保持垂直,其傾斜角不大于 5°如圖四所示;
⑺ 控制箱內(nèi)正對出風口的電器元件與出風口的最小距離應大于200mm,因距離太近電器元件表面易產(chǎn)生水膜現(xiàn)象,從而導致電器故障的發(fā)生。若無法避免,請在電器元件前增加一塊隔熱材料;并且箱內(nèi)出風口四周的電器元件與出風口應保持一定的距離,以便減小箱內(nèi)空氣的流通阻力。⑻ 當空調(diào)器工作時,電控箱四周應該密封,箱門盡量較少打開次數(shù),以便箱體內(nèi)空氣的溫、濕度能控制在較為理想的狀態(tài)下。
圖三
電控箱冷氣機圖四錯 誤 正 確 錯 誤 正 確
2-2 安裝方法
⑴ 當機組在搬運、裝卸時,請始終保持設備處于垂直直立狀態(tài),不要將設備長期放在露天場所;⑵ 為使空調(diào)器的冷卻效果最佳,請將機組直接安裝在電氣柜的外壁上,請勿采用風管的形式進行送風,如若確實需要采用風管送風,請先咨詢本公司技術工程師;⑶ 空調(diào)器在安裝之前,請先確認好安裝位置的強度是否能承載機組,以免造成人員受傷及設備損壞,當安裝在電氣柜門上時,最好該扇箱門能固定不動,當需要打開時請先確認好加在門上的重量不會使整個電氣柜傾倒;
⑷ 電氣柜上必須開孔,以便使冷風能進入電控箱內(nèi),具體的開口尺寸請參見圖五;⑸ 箱體開孔時請嚴格參照開口尺寸進行,孔口處的毛刺必須清除,以免劃傷機組;⑹ 當長期使用時請注意安裝螺栓是否損壞或脫落,若有而未加處理,將有可能導致機器掉落而損壞;
⑺ 具體的安裝方式如下
安裝示意圖:
2-3 電器配線:
⑴ 機組安裝好后請先檢查電源電壓值是否保持在容許額定值內(nèi),請避免電壓值過高或過低,若所提供的電壓在額定值±10%以內(nèi),本機組可正常使用;L,N,PE ,為電源輸入引線經(jīng)常在超過額定電壓值的環(huán)境中使用,將會大大縮短壓縮機和其他電氣設備及元件的使用壽命,此類損壞不屬于我公司包修范圍,只負責收費維修。請用戶千萬注意⑵ 空調(diào)的電器箱在機體內(nèi)部,非專業(yè)維修人員請勿打開電器箱進行操作。機組引出一根電源線,當安裝好后無需另外接線,將插頭插入電控箱內(nèi)的電源插座即可;⑶ 在機組的電器回路上請自行安裝斷路器或漏電保護裝置;⑷ 請準備本機專用電源插座,不要在同一個插座上使用過多電器裝置,否則容易使電源超出負載,引發(fā)事故。
2-4 機器排水:(戶外機型無以下排水管項目)
本機器自身有除濕功能,當機器運行時,它會慢慢除去電控箱內(nèi)空氣中的部分水分,這部分水氣就會以液態(tài)的形式排出,排水管就起到排出這部分水的作用,排水管的連接請注意以下幾點:⑴ 請先在機器排水口上連接好短接頭,然后把配給的軟管連接上,再用抱箍緊固好連接處;⑵ 根據(jù)實際情況排水軟管長度適當即可,過長部分請切除;⑶ 排水軟管請勿折彎、壓扁、阻塞或出口高于進口,以免排水不暢,從而導致機器內(nèi)產(chǎn)生淤水
嚴重時產(chǎn)生外溢,引起空調(diào)器或者電氣柜故障。
啟動與運行 3-1 運行前后注意事項
⑴ 啟動前請先檢查排水管是否已經(jīng)連接到位,電控箱門是否關嚴,若均已到位即可插上電源開始工作;(戶外機型無排水管,直接在底部有漏水孔)
⑵ 當在運轉中需重新啟動空調(diào)器時,請間隔 3 分鐘以上,倘若頻繁啟動且間隔時間過短會引起機器損傷;
⑶ 當空調(diào)器傾斜時請勿開啟,避免漏水、觸電等情況發(fā)生;⑷ 空調(diào)器在出廠時溫度點已經(jīng)設定好為 30℃,若需重新設定時請控制在允許范圍之內(nèi)設定,以免引起機器運行不正常;如果空調(diào)器有加熱功能,出廠時設置為5℃⑸ 當機器有異常噪音或異味(焦臭)等現(xiàn)象出現(xiàn)時,請馬上關閉空調(diào)器,并請專業(yè)人員進行檢查維修。
3-2 機器操作說明:系統(tǒng)參數(shù)設置界面進入:
使用一組密碼進入?yún)?shù)設置狀態(tài)(出廠默認密碼為1111),按〖P〗鍵并保持3秒鐘,數(shù)碼管顯示『---0』,按〖▼〗鍵循環(huán)選擇密碼當前位,按〖▲〗鍵設置當前位密碼值,密碼設置完成后按〖S〗鍵確認。如果密碼錯誤,顯示『Err』蜂鳴器響三聲后退出參數(shù)設置狀態(tài);如果密碼輸入正確,蜂鳴器響一聲,進入?yún)?shù)設置狀態(tài),這時數(shù)碼管顯示『U10』,用〖▲〗或〖▼〗鍵選擇參數(shù)代碼,選定一個參數(shù)后按〖S〗鍵顯示該參數(shù)的設定值,這時再按〖▲〗或〖▼〗鍵可對參數(shù)進行設置,設置完成后再按〖S〗鍵,回到顯示參數(shù)代碼狀態(tài)。·系統(tǒng)參數(shù)設置界面退出:
當參數(shù)設置完成后必須長按〖P〗鍵 3 秒, 系統(tǒng)退出參數(shù)設置狀態(tài),此次參數(shù)設置被保存。在參數(shù)設置狀態(tài)如果連續(xù) 30 秒內(nèi)無按鍵操作,系統(tǒng)退出參數(shù)設置狀態(tài),但此次參數(shù)設置無效,控制器仍按原來的參數(shù)運行;
顯示屏信號說明
面板數(shù)碼管說明
4 位紅色數(shù)碼管顯示測量溫度值和告警代碼;
圖標 功能 亮 滅 閃爍壓縮機 啟動 停止
準備制冷,壓縮機正在延時保護AUX 電加熱 運行 ---- ----風機 運行 停止 ----維修 有故障 無故障 ----報警 有告警 無報警 ----通訊 ---- ---- 正在通訊HACCP 壓縮機強
制
強制運行 ---- ----序 號 顯示代碼 說 明
1 “E01” 溫控傳感器故障(短路或斷路)
3 “E02” 蒸發(fā)器傳感器故障(短路或斷路)
3 “E03” 系統(tǒng)缺氟保護
4 “Hi” 高溫告警
5 “Lo” 低溫告警
6 “EE” 數(shù)據(jù)存取錯誤
7 “Err” 密碼輸入錯誤
8 “iA” 外部無源數(shù)字量輸入告警(系統(tǒng)高壓告警)
9 “UnL” 恢復默認出廠密碼“1111”
10 “FrE 蒸發(fā)器凍結保護
序
號
參數(shù)代
碼
設置功能 設定范圍 說明
出廠設定值00 U00 制冷溫度設定 25~ 40℃ 30
01 U01 制熱溫度設定 1~ 20℃ 5
02 U02 溫差 1.0~ 5.0℃ 3
03 U03 高溫報警溫度
-5.0~50℃
高 溫 / 低 溫 設 定間隔1℃
50
04 U04 低溫報警溫度 5
05 U05 蒸發(fā)風機溫度設定 0~40℃ 26
06 U06 蒸發(fā)風機溫差 1.0~ 5.0℃ 2
07 U10 溫控探頭校正
-3.0~+3.0
℃
0
08 U11 蒸發(fā)器探頭校正
-3.0~+3.0
℃
0
09 U12 高溫報警失效 0~1 0:禁用;1:啟用1
10 U13 低溫報警失效 0~1 0:禁用;1:啟用1
11 U14 系統(tǒng)缺氟失效 0~1 0:禁用;1:啟用1
12 U21
蒸發(fā)器探頭使能設
定
0~1 0:禁用;1:啟用1
13 U22 壓縮機工作模式 0~1
0:自動模式(啟用壓縮機)
1:禁用模式
0
15 U26 外部輸入告警模式 0~1
0:常閉;
1:常開
0
16 U28 蜂鳴器報警 0~1 0:禁用;1:啟用1
17 U29
壓縮機開機延時時
間
1~5 分鐘 3
18 U30
壓縮機最短持續(xù)運
行時間
1~5 分鐘 3
19 U34 RS485 波特率設定 0~3
0:2400bps
1:4800bps
2:9600bps
3:19200bps
3
20 U35 設備地址 1~99 1
21 U99 密碼
0000 ~
9999
---- 1111
22 End 設定結束
控制功能說明:
壓縮機控制
◇當測量溫度 ≥【制冷設定溫度】 + 【溫差】,且壓縮機停機時間大于【壓縮機開機延時時間】,壓縮機開啟;◇當測量溫度 ≤【設定溫度】,且壓縮機開機時間大于【壓縮機最短持續(xù)運行時間】,壓縮機關閉;例如:【制冷設定溫度】為 25 度, 【溫差】為 2 度,則當溫控傳感器檢測溫度高于27 度時啟動壓縮機,溫度低于 25 度時關閉壓縮機,將溫度控制在 25~27 度之間;
◇壓縮機強制啟動:
1.在壓縮機關閉情況下,按住〖▼〗鍵 5 秒不放,可以強制啟動壓縮機。在壓縮機強制啟動狀態(tài)下,按住〖▼〗鍵5
秒不放,可以取消強制啟動壓縮機,壓縮機恢復正常運行。
2.壓縮機在強制啟動狀態(tài)下持續(xù)運行 60min 后,壓縮機恢復正常運行。
壓縮機延時保護
◇運行過程中壓縮機停機,必須經(jīng)過【壓縮機開機延時時間】才能再次啟動;
◇運行過程中壓縮機開啟,必須經(jīng)過【壓縮機最短持續(xù)運行時間】才能以實際情況停機;電加熱器控制: [加熱型]
◇當測量溫度 ≤ 【制熱設定溫度】 - 【溫差】, 電加熱開啟;
◇當測量溫度 ≥ 【制熱設定溫度】, 電加熱關閉;
例如:【制熱設定溫度】為 10 度, 【溫差】為 2 度,則當溫控傳感器檢測溫度低于8 度時啟動電加熱,溫度高于 10 度時關閉電加熱,將溫度控制在 8~10 度之間;
電加熱的開啟和壓縮機的開啟為互斥關系;
4.維護與保養(yǎng)
請定期檢查排水管,并確定無堵塞現(xiàn)象,若排水不良易造成空調(diào)器漏水。請定期清洗空氣過濾網(wǎng)和冷凝器。對于機器上安裝的是尼龍濾網(wǎng)的可直接從側面拔出(戶外機型底部有漏水孔)
4-1 定期清潔
本機的濾網(wǎng)材質(zhì)為尼龍濾網(wǎng),可直接從網(wǎng)罩上面拉出,用洗滌水清洗干凈,并晾干后按原樣裝回,一般每周需清洗一次; 有的機型為鈑金的網(wǎng)孔,直接用氣槍清洗即可。⑵ 請用中性清洗劑擦拭機體,避免使用硬刷及酸性清洗劑清洗,嚴禁用水沖洗空調(diào)器,以防發(fā)生觸電事故;
4-2 長時間停用時注意
⑴ 請切斷電源,以防意外;
⑵ 清理冷凝器、過濾網(wǎng)及內(nèi)部油污;
⑶ 請對機器采取防塵措施,延長機器使用壽命。
2. 故障排除
故障狀況 1 電源接通后,室內(nèi)、室外風機不運轉
可能原因
※保險絲熔斷
※停電或無電源
狀況排除
※更換保險絲
※檢查電源狀況
故障狀況 2 在運行中突然停機,電控箱內(nèi)溫度高于設定點溫度兩度以上可能原因
※環(huán)境溫度過高,導致壓縮機熱保護
※過濾網(wǎng)堵塞或者冷凝器過臟,導致壓縮機熱保護
狀況排除
※改善周邊環(huán)境,使散熱暢通
※對過濾器及冷凝器進行清洗
故障狀況 3 機器正常運轉,卻不制冷
可能原因
※壓縮機損壞
※制冷系統(tǒng)泄露
※機組蒸發(fā)器大面積結霜
狀況排除
※更換壓縮機,重新抽真空充注制冷劑
※查出泄露處,并重新抽真空加制冷劑
※立即停機,把設定溫度調(diào)高到 35℃,十分鐘后重新開機◇若上述措施均不能排除故障,請致電本公司咨詢!
附錄 1:產(chǎn)品技術參數(shù)
型號:KBCW-600GR
工作電源: 交流 220V ±10% 頻率 50Hz ±4%
運行電流: <1.82A
制冷功率:350W 加熱功率:520W
制冷劑: R134a
制冷量: 600W 加熱量:500W
防護等級:內(nèi)循環(huán):IP45 外循環(huán):IP55
允許機柜內(nèi)溫度設定范圍:30--38℃(出廠設定 30℃)
允許使用環(huán)境溫度范圍:-25--45℃
噪音:55dB
附錄 2:電氣原理圖
室內(nèi)風機 室外風機 壓縮機
M1 M2 M3
C2 C3
L
N
PE
t℃溫控器
KBCW-6主00回GR路電路圖 控制回路溫
控
器
昆 山 科諾泰電氣設備有限公司地址:蘇州市昆山市張浦鎮(zhèn)垌坵路199 號聯(lián)系電話:18121419046