佛山鎧耐空調(diào)設備有限公司建筑冷熱源一體化解決專家 第1頁/共24頁目錄1、致用戶··························································································22、產(chǎn)品簡介·······················································································33、電氣控制及安裝··············································································44、機組安裝·······················································································125、運行調(diào)試······················································································... [收起]
[展開]
低溫變頻機組(科萊泰克)2023
粉絲: {{bookData.followerCount}}
文本內(nèi)容
第1頁

佛山鎧耐空調(diào)設備有限公司建筑冷熱源一體化解決專家 第1頁/共24頁目錄1、致用戶··························································································22、產(chǎn)品簡介·······················································································33、電氣控制及安裝··············································································44、機組安裝·······················································································125、運行調(diào)試·······················································································156、故障代碼表及解決措施·····································································167、維護保養(yǎng)·······················································································208、機組參數(shù)·······················································································229、熱泵基本原理·················································································24警告1. 機組拆箱后,請檢查制冷系統(tǒng)的壓力。如壓力低于 0.2Mpa,不得進行后續(xù)的安裝工作,請聯(lián)系經(jīng)銷商,檢查系統(tǒng)的氣密性。

2. 開機前先核對銘牌內(nèi)電源規(guī)格與實際送電必須相符,并預熱 6 個小時后,才能開機。3. 主機出廠前已在本廠測試完畢,所以安全保護開關(guān)均已設定妥當,用戶切勿自行調(diào)整。

4. 檢修時請斷開機組電源,不可帶電操作,以免機組啟動造成人員傷亡。5. 機組冬季停止運行時,機組絕對不能斷電,防止機組凍壞。

6. 冬季長期停機時應排放干凈系統(tǒng)里的水,以防止機組凍壞。

第2頁

佛山鎧耐空調(diào)設備有限公司第 2頁/共 24頁 建筑冷熱源一體化解決專家

致 用 戶

1、 歡迎購買科萊泰克泵機組產(chǎn)品,在安裝使用本設備之前,請閱讀本手冊,閱讀后,請妥善保管好本手冊,以備以后參考。安裝和維修需要熟悉國家和當?shù)匕踩?guī)范的專業(yè)人員承擔。如果在安裝維修及使用中未能遵守本手冊所包含的說明和注意事項及安全規(guī)范,可能會導致設備的損壞或財產(chǎn)損失,并且有可能造成操作人員的傷害。最好的預防是正確的安裝、正確的操作和經(jīng)常性的維護與保養(yǎng)。2、 由于科萊泰克將不斷改進產(chǎn)品質(zhì)量及性能,保留未經(jīng)通知更改產(chǎn)品型號的權(quán)力,并不因此承擔任何義務。

3、 在閱讀本手冊中,如果您需技術(shù)咨詢,請您與科萊泰克公司或當?shù)劁N售商聯(lián)系。注意:一旦發(fā)生器具以外的接地系統(tǒng)異常情況時,應立即停止使用熱泵機組。并拔下其電源插頭或斷開與供電電路的一切連接,并與制造廠的維修人員聯(lián)系處理。

第3頁

佛山鎧耐空調(diào)設備有限公司建筑冷熱源一體化解決專家 第3頁/共24頁產(chǎn)品簡介安全可靠

科萊泰克熱泵機組是使用電力但不利用電力加熱的熱水裝置。因為不使用電力直接加熱,水電完全隔離,安全系數(shù)進一步提高。它沒有電熱泵機組、燃氣熱泵機組使用中存在的易觸電、易燃、易爆、易中毒等安全問題,是當今較為安全的熱水供給設備。高效省電

科萊泰克熱泵機組采用熱泵制熱,從空氣中獲得大量的免費熱能,因此提供相同的熱水量,用電量僅僅是傳統(tǒng)電熱泵機組的四分之一左右,可為用戶省下大筆的用電費用。綠色環(huán)保

科萊泰克熱泵機組采用太陽能、空氣熱能和電能三種干凈能源,沒有使用油、煤、氣等礦物燃料所造成的環(huán)境污染。它在工作過程中沒有排放有害氣體,用戶即使在密閉的空間里沐浴,也不用擔心人體健康方面的問題。

全天候使用

熱泵機組不受陰、雨等惡劣天氣的影響,一天二十四小時能全天候使用,彌補了一般太陽能受天氣環(huán)境影響,不能保證一年三百六十五天隨時供應熱水的缺點。且安裝有精確的水溫控制系統(tǒng),保證在沐浴過程中有恒定水溫。

長久耐用

科萊泰克熱泵機組使用的壓縮機、四通閥等主要零配件采用世界名廠生產(chǎn)的優(yōu)質(zhì)產(chǎn)品,再加以合理完善的生產(chǎn)工藝、嚴格的質(zhì)檢手段,使機組的性能完全得到了可靠保證。且經(jīng)過嚴謹?shù)臏y試,其使用壽命長達十年以上,遠高于其它類型熱泵機組的使用壽命。安裝簡單

科萊泰克熱泵機組安裝簡便,且不受環(huán)境限制,可安裝在樓頂、陽臺、車庫、廚房、儲物間、地下室等地方,不須專人看管,不須設置專用機房。操作簡便,智能化運行安全可靠

智能化運行,可根據(jù)負荷變化自動調(diào)整投入運行的機組數(shù)量,實現(xiàn)最佳節(jié)能運行。完善可靠的全自動控制系統(tǒng),同時機組設計配有多種保護措施,并有自動防凍、自動除霜等多種控制,使機組運行安全可靠,操作更為簡單。

應用廣泛

熱泵機組可滿足普通家庭和工廠、學校、賓館、酒樓、醫(yī)院、美容院、洗衣店、洗浴中心等單位的需求,為用戶提供源源不斷的生活、生產(chǎn)所需熱水。

第4頁

佛山鎧耐空調(diào)設備有限公司第 4頁/共 24頁 建筑冷熱源一體化解決專家

電 氣 控 制 及 安 裝

一、操作面板

名稱 符號 狀態(tài) 功能或含義熱水符號 常亮 制熱狀態(tài)

化霜符號 常亮 化霜狀態(tài)

壓縮機符號 常亮 壓縮機運行中風機符號 常亮 風機運行中

水泵符號 常亮 水泵運行中

電輔熱符號 常亮 電輔熱運行中(正常)電輔熱符號 閃爍 電輔熱運行中(速熱)攝氏度符號 常亮 當前顯示的是攝氏溫度時間符號 常亮 顯示當前的一個實時時間定時時段 1 符號 常亮 設置定時時段1 的時間定時時段 2 符號 常亮 設置定時時段2 的時間定時符號 常亮 定時開關(guān)機開啟中制冷圖標

制熱模式圖標

時鐘/定時/功能顯示

鎖屏圖標

化霜進入圖標定時開標志定時關(guān)標志溫度顯示圖標熱水模式

第5頁

佛山鎧耐空調(diào)設備有限公司建筑冷熱源一體化解決專家 第5頁/共24頁電氣控制及安裝名稱 符號 狀態(tài) 功能或含義鎖鍵符號 常亮 當前按鍵已鎖定二、按鍵功能

序號 按鍵名稱 圖標 功能描述1 開關(guān)鍵

開關(guān)機;

2 功能鍵

模式切換

3 定時鍵

時鐘設置;定時開關(guān)機設置4 加鍵

水溫+或翻頁5 減鍵

水溫-或翻頁6 鎖定鍵

按鍵鎖定

7 組合鍵 “ ”+“ ” 強制“化霜”開啟或關(guān)閉1. 線控操作

2.1 開機和關(guān)機

在主界面時,長按“開/關(guān)”鍵 3 秒可切換開/關(guān)機。

鎖鍵時,長按“開/關(guān)”鍵 3 秒可進行解鎖操作。

2.2 設定溫調(diào)節(jié):

2.2.1 開機制熱時,可對進水水溫進行調(diào)節(jié),在主界面按”△”“▽”鍵即可調(diào)節(jié)所需制熱溫度。2.2.2 開機制冷時,可對進水水溫進行調(diào)節(jié),在主界面按”△”“▽”鍵即可調(diào)節(jié)所需制冷溫度。2.3 機組狀態(tài)查詢

在主界面時,長按“▽”鍵 3 秒可進入查看溫度參數(shù)。如下表

機組狀態(tài)表:

查詢代碼 代表意義 顯示范圍01 進水溫度 -30~99℃02 出水溫度 -30~99℃

第6頁

佛山鎧耐空調(diào)設備有限公司第 6頁/共 24頁 建筑冷熱源一體化解決專家

電氣控制及安裝查詢代碼 代表意義 顯示范圍03 環(huán)境溫度 -30~99℃04 排氣溫度 0~125℃05 回氣溫度 -30~99℃06 外盤管溫度 -30~99℃07 經(jīng)濟器進溫度 -30~99℃08 經(jīng)濟器出溫度 -30~99℃09 內(nèi)盤管溫度 -30~99℃10 主膨脹閥開度

11 增焓膨脹閥開度

12 壓機電流

13 散熱片溫度

14 直流母線電壓值

15 壓機實際頻率

16 直流風機風速

17 預留

18 故障記錄 1 上電清除記錄19 故障記錄 2 上電清除記錄20 故障記錄 3 上電清除記錄2.4 時鐘設定:

長按【定時】鍵 3 秒后進入時鐘閃爍狀態(tài),此時再按一下【定時】鍵便可進入時鐘設置狀態(tài),首先是小時位閃爍,表示可以通過”△”“▽”鍵調(diào)整當前時間的小時值。每按1 次”△”鍵小時加一,每按 1 次 “▽”鍵小時減一。設置好小時位數(shù)值后,再按一下【定時】鍵;此時分鐘位閃爍,表示可以通過”△”“▽”鍵調(diào)整當前時間的分鐘值。設置好分鐘位數(shù)值后,再按一下【定時】鍵結(jié)束。2.5 定時設定:

按一下【定時】鍵進入時段選擇,此時顯示“時段 1”,按”△”“▽”鍵可選擇不同的時段進行設置;

再按一下【定時】鍵進入時段 1 設置,按”△”“▽”鍵可修改定時時間;其它時段設置依次類推;在定時設置界面中,長按一下“定時”鍵 5 秒,則取消當段定時開/關(guān);2.6 系統(tǒng)參數(shù)設置

長按”△”鍵 3 秒可進入?yún)?shù)查詢狀態(tài),按”△”或”▽”鍵查詢參數(shù),然后按“功能鍵”后可通過”△”或”▽”鍵更改參數(shù),更改完成按“功能鍵”確認并退回到查看狀態(tài)。

第7頁

佛山鎧耐空調(diào)設備有限公司建筑冷熱源一體化解決專家 第7頁/共24頁電 氣 控 制 及 安 裝

系統(tǒng)參數(shù)表:

設置代碼 參數(shù)名稱 調(diào)整范圍 初始值P01 空調(diào)回差溫度 1℃~18℃ 3℃P04 制冷設定溫度 7℃~30℃ 12℃P05 制熱設定溫度 15℃~50℃ 45℃P09 進水溫度補償 -5℃~15℃ 0℃P11 除霜周期 20MIN~90MIN 45MIN

P12 除霜進入溫度 -15℃~-1℃ -3℃P13 除霜時間 5MIN~20MIN 10MIN

P14 除霜退出溫度 1℃~40℃ 20℃P15 除霜的環(huán)境與盤管溫差 0℃~15℃ 8℃P16 除霜的環(huán)境溫度 0℃~20℃ 17℃P17 主膨脹閥動作周期 20S~90S 20S

P18 主膨脹閥制熱目標過熱度 -5℃~10℃ -2℃P19 主膨脹閥調(diào)節(jié)的排氣溫度 70℃~125℃ 95℃P20 除霜膨脹閥開度 20~450 400

P21 主膨脹閥最小開度 50~150 50

P22 主膨脹閥模式選擇 0-自動/1-手動 0

P23 主膨脹閥的手動步數(shù) 20~450 350

P24 制冷目標過熱度 -5℃~10℃ -1℃P25 輔膨脹閥的手動步數(shù) 20~450 350

P26 增焓電磁閥開啟環(huán)境溫度 11℃~45℃ 23℃P28 恒溫水泵模式:1-不停/0-停 0~1 0

P29 輔膨脹閥排氣比例系數(shù) 1~6 2

P30 輔膨脹閥排氣微分系數(shù) 0~180 1

P31 輔膨脹閥過熱度比例系數(shù) 1~6 2

P32 輔膨脹閥過熱度微分系數(shù) 0~180 1

P33 輔膨脹閥調(diào)節(jié)周期 10~20 15

P34 輔膨脹閥目標排氣溫度 90~120 95

P35 關(guān)閉輔膨脹閥排氣溫度 40~70 60

P36 輔膨脹閥目標過熱度 -10~10 4

P37 輔膨脹閥模式選擇 0-自動/1-手動 0

P38 主膨脹閥過熱度比例系數(shù) 1~6 5

P39 主膨脹閥過熱度微分系數(shù) 1~180 1

注:參數(shù) P29,P31 ,P38 實際使用的值是除以 10(即范圍為 0.1~0.6)2.7 模式轉(zhuǎn)換

在開機狀態(tài)主界面時,長按“功能”鍵 3 秒可切換工作模式;2.8 強制除霜功能

長按“功能”+“▽”鍵 3 秒進入強制除霜;

第8頁

佛山鎧耐空調(diào)設備有限公司第 8頁/共 24頁 建筑冷熱源一體化解決專家

電 氣 控 制 及 安 裝

2.9 恢復出廠參數(shù)

長按“功能”+“定時”+“△”+“▽” 鍵 3 秒進入恢復出廠參數(shù)。2.10 變頻參數(shù)設置

長按【開關(guān)】+【定時】鍵 5 秒進入密碼輸入狀態(tài),顯示“0000”,按”△”或”▽”鍵可輸入密碼,再

按【定時】鍵可切換密碼位。輸入不同密碼分別進入以下幾種狀態(tài):

輸入 4 位密碼“9615”,輸入完成后按【功能】鍵確定則進入手動頻率設置狀態(tài),直接按“△”“▽” 鍵調(diào)整手動頻率,重復此操作或重新上電則退出手動設置頻率模式。輸入 4 位密碼“8866”,輸入完成后按【功能】鍵確定則進入頻率查看狀態(tài),原來的“小時”顯示“目標頻率”,原來的“分鐘”顯示“運行頻率”,重復此操作或重新上電則退出該狀態(tài)。輸入 4 位密碼“4180”,輸入完成后按【功能】鍵確定,若密碼輸入正確則進入變頻參數(shù)設置.一、 模式運行

1. 制冷模式

進水溫度≥制冷設定溫度+回差溫度時,開機制冷;

當參數(shù) 117 選為 0 時,進水溫度≤制冷設定溫度時,停止制冷;

當參數(shù) 117 選為 1 時,進水溫度≤制冷設定溫度時,恒溫控制,直至進水溫度≤制冷設定溫度-2℃,停止制冷;

2. 制熱模式

進水溫度≤制熱設定溫度-回差溫度時,開機制熱;

當參數(shù) 117 選為 0 時,進水溫度≥制熱設定,停止制熱;

當參數(shù) 117 選為 1 時,進水溫度≥制熱設定溫度時,恒溫控制,直至進水溫度≥制熱設定溫度+2℃,停止制熱;

3. 除霜運行

? 制熱進入除霜條件:

制熱時,壓機累計運行時間≥45MIN(參數(shù) P11),且壓機持續(xù)運行時間≥5min;外盤管溫度<-3℃(參數(shù) P12);

1 (環(huán)境溫度-外盤管溫度)≥5℃(參數(shù) P15),且-7℃≤環(huán)境溫度≤參數(shù)P16 并持續(xù)30秒;2 (環(huán)境溫度-外盤管溫度)≥5℃(參數(shù) P15),且環(huán)境溫度<-7℃并持續(xù)30 秒;同時滿足以上條件時,則進入除霜;(注:①和②只需滿足任一條件即可)當外盤管溫度故障時,若環(huán)境溫度≤20℃,則除霜改為定時除霜,除霜時間為10MIN;? 啟動時進入除霜條件:

當停機/待機/壓機斷電時間≥30min 時;

-7℃≤環(huán)境溫度≤3℃,且盤管溫度<參數(shù) P12;

在滿足壓縮機啟動條件(水溫低于回差/開機啟動機器,但未啟動)時,以上條件滿足時進入除霜運行。

? 退出除霜條件:

第9頁

佛山鎧耐空調(diào)設備有限公司建筑冷熱源一體化解決專家 第9頁/共24頁電 氣 控 制 及 安 裝

當外盤管溫度≥20℃(參數(shù) P14)或除霜時間達到 10MIN(參數(shù)P13)時,則系統(tǒng)退出除霜;? 除霜動作:(除霜時不關(guān)壓機,只是把頻率降到最低 30Hz)

進入除霜條件滿足時進行下列動作:

1) 壓機降到 30HZ,15 秒之后風機關(guān);

2) 55S 時四通閥上電;

3) 60S 時壓機升到除霜頻率 60HZ;

4) 水泵保持運行;

退出除霜條件滿足時進行下列動作:

1) 壓機降到 30HZ;

2) 55S 時四通閥失電;

3) 60S 時風機開,5 秒之后壓機回到正??刂祁l率,恢復正常制熱運行;? 除霜的非正常結(jié)束:

1) 在除霜期間出現(xiàn)故障保護停機時,系統(tǒng)立即退出除霜,停止運行;2) 在除霜期間不檢測低壓保護;

強制除霜:在外盤管溫度低于退出除霜溫度時,長按 M+▽鍵 3 秒可進入強制除霜;二、 各種負載的控制

1. 壓縮機

? 壓縮機根據(jù)受控溫度和設定溫度值來決定開/關(guān);

? 壓縮機關(guān)機之后,至少要間隔 3 分鐘才能開;

? 首次上電無 3 分鐘保護;

壓機

3 分鐘停機保護

關(guān) 時間2. 水泵

? 開機時,水泵提前壓機 30 秒運行;關(guān)機時,水泵延后壓機 30 秒關(guān)閉;3. 風機

? 開機時,風機提前壓機 5 秒開;關(guān)機時,風機延后壓機 30 秒關(guān);? 在除霜時,風機停止運行。

4. 四通閥

? 當參數(shù) P27=0 時,四通閥正向:

? 正常制熱、關(guān)機時,四通閥失電;

? 正常制冷、除霜時,四通閥得電;

? 當參數(shù) P27=1 時,四通閥反向:

? 正常制熱,四通閥得電;

? 正常制冷、除霜、關(guān)機時,四通閥失電;

5. 曲軸電加熱

? 當環(huán)境溫度≤7℃且壓機關(guān)閉時,曲軸電加熱開啟;

? 當環(huán)境溫度≥9℃或壓機開啟時,曲軸電加熱關(guān)閉;

6. 增焓電磁閥

制熱模式:

第10頁

佛山鎧耐空調(diào)設備有限公司第 10頁/共 24頁 建筑冷熱源一體化解決專家

電 氣 控 制 及 安 裝

? 當排氣溫度≥100℃,增焓閥強制開啟;當排氣溫度≤95℃時按環(huán)境溫度控制:? 當環(huán)境溫度≤參數(shù) P26,增焓閥開啟;當環(huán)境溫度≥參數(shù) P26+2℃,增焓閥關(guān)閉;7. 底盤電加熱

制熱時,環(huán)境溫度≤2℃打開,環(huán)境溫度≥4℃關(guān)閉。除霜時候強制打開。8. 輔助電加熱

? 控制邏輯如下:

? 啟動條件:

1) 制熱模式下;

2) 環(huán)境溫度<0℃ 或環(huán)境溫感故障

3) 制熱有需求,即進水溫度≤制熱設定溫度-回差溫度(參數(shù)P1)時;4) 水泵處于運行狀態(tài)

以上條件同時滿足時電輔熱開啟。

? 關(guān)閉條件:

1) 制冷模式下;

2) 制熱無需求或恒溫控制時;

3) 進水溫度傳感器出現(xiàn)故障報警;

4) 環(huán)境溫度>0℃

5) 水流故障

6) 水泵關(guān)閉

以上任何一條件滿足時,電輔熱停止

? 電輔熱開啟,水泵提前 30s 開啟;輔助電加熱關(guān)閉,水泵延時30s 關(guān)閉。? 除霜、強制除霜、二級防凍時,強制開啟電加熱;

? 高壓故障、低壓故障、排氣溫感故障、排氣過高保護停機時,若壓機鎖定不能啟動時,5分鐘后則啟動電加熱代替壓機運行。三、 系統(tǒng)保護功能

1) 通信故障

? 當主板與線控通信斷開 60 秒時,則報通信故障(Er09),機組繼續(xù)運行;2) 環(huán)境溫度故障

? 機組上電后檢測;

? 任意時刻檢測到環(huán)境溫度溫感短路或斷路,則判斷為環(huán)境溫度溫感故障,系統(tǒng)不停機;? 發(fā)生此故障時,相應防凍條件取消;

? 此故障可自動恢復;

? 故障時線控器報維修故障;

3) 進水溫度故障

? 機組上電后檢測;

? 任意時刻檢測到進水溫感短路或斷路,則判斷為進水溫感故障,系統(tǒng)停機保護;? 此故障可自動恢復;

? 故障時線控器報維修故障;

4) 出水溫度故障

? 機組上電后檢測;

第11頁

佛山鎧耐空調(diào)設備有限公司建筑冷熱源一體化解決專家 第11頁/共24頁電 氣 控 制 及 安 裝

? 任意時刻檢測到出水溫度溫感短路或斷路,則判斷為出水溫度溫感故障,系統(tǒng)停機保護;? 發(fā)生此故障時,相應防凍條件取消;

? 此故障可自動恢復;

? 故障時線控器報維修故障;

5) 外盤管溫度故障

? 機組上電后檢測;

? 任意時刻檢測到外盤管溫感短路或斷路,則判斷為外盤管溫感故障,系統(tǒng)不停機;? 發(fā)生此故障時,在制熱模式下主路電子膨脹閥開至手動步數(shù);? 此故障可自動恢復,發(fā)生此故障時除霜為定時除霜;

? 故障時線控器報維修故障;

6) 內(nèi)盤管溫度故障

? 機組上電后檢測;

? 任意時刻檢測到內(nèi)盤管溫感短路或斷路,則判斷為內(nèi)盤管溫感故障,系統(tǒng)不停機;? 發(fā)生此故障時,在制冷模式下主路電子膨脹閥開至手動步數(shù);? 此故障可自動恢復;

? 故障時線控器報維修故障。

7) 經(jīng)濟器進溫度故障

? 機組上電后檢測;

? 任意時刻檢測到經(jīng)濟器進溫感短路或斷路,則判斷為經(jīng)濟器進溫感故障,系統(tǒng)不停機;? 此故障可自動恢復;

? 故障時線控器報維修故障。

8) 經(jīng)濟器出溫度故障

? 機組上電后檢測;

? 任意時刻檢測到經(jīng)濟器出溫感短路或斷路,則判斷為經(jīng)濟器出溫感故障,系統(tǒng)不停機;? 此故障可自動恢復;

? 故障時線控器報維修故障。

9) 回氣溫度故障

? 機組上電后檢測;

? 任意時刻檢測到回氣溫感短路或斷路,則判斷為回氣溫感故障,系統(tǒng)不停機;? 發(fā)生此故障時,主路電子膨脹閥開至手動步數(shù);

? 此故障可自動恢復;

? 故障時線控器報維修故障;

10) 排氣溫度故障

? 壓機開啟 5 分鐘后檢測到排氣溫感短路或斷路,則判斷為排氣溫感故障,系統(tǒng)停機保護;? 此故障可自動恢復;

? 故障時線控器報維修故障;

11) 系統(tǒng)高壓保護

第12頁

佛山鎧耐空調(diào)設備有限公司第 12頁/共 24頁 建筑冷熱源一體化解決專家

電 氣 控 制 及 安 裝

? 壓機開啟后,連續(xù) 5S 檢測到高壓開關(guān)斷開,則系統(tǒng)停機保護;? 60 分鐘內(nèi)發(fā)生三次此故障,則非掉電不可恢復(前兩次可自動恢復);? 故障時線控器報維修故障,

12) 系統(tǒng)低壓保護

? 壓機開啟 5 分鐘后,連續(xù) 5 秒檢測到低壓開關(guān)斷開,則系統(tǒng)停機保護;? 60 分鐘內(nèi)發(fā)生三次此故障,則非掉電不可恢復(前兩次可自動恢復);? 故障時線控器報維修故障;

13) 排氣溫度過高保護

? 壓機開啟 1 分鐘后檢測排氣溫度,當檢測到排氣溫度≥120℃(參數(shù)P06)時,則進入排氣過高保護,系統(tǒng)停機;

? 當檢測到排氣溫度≤95℃(參數(shù) P07)時,則退出排氣過高保護,恢復正常運行;? 60 分鐘內(nèi)發(fā)生三次此故障,則非掉電不可恢復(前兩次可自動恢復);? 故障時線控器報維修故障;

14) 制冷出水過冷保護

? 在制冷時,壓機開啟 5 分鐘后檢測出水溫度,當連續(xù) 5 秒檢測到出水溫度≤5℃時,則進入制冷過冷保護,壓機和風機停止運行,水泵運行根據(jù) P28 決定;? 當檢測到出水溫度≥7℃時,則退出制冷過冷保護,恢復正常運行;? 故障時線控器報維修故障;

15) 制熱出水過高保護

? 在制熱時,當檢測到出水溫度≥75℃時,則進入制熱過熱保護,壓機和風機停止運行,水泵運行根據(jù) P28 決定;

? 當檢測到出水溫度≤70℃時,則退出制熱過熱保護,恢復正常運行;? 故障時線控器報維修故障;

16) 水流保護

? 水泵啟動 15 秒后檢測水流開關(guān),連續(xù) 10 秒檢測到此開關(guān)斷開,則停機保護;? 發(fā)生此故障時,如故障未恢復,則每隔 4 分鐘重新啟動水泵運行,檢測水流情況,當60分鐘內(nèi)自動重啟水泵 5 次后水流開關(guān)仍未閉合則不再啟動水泵,直到水流開關(guān)閉合后才能再次啟動水泵;

? 水流故障時線控器報維修故障;

17) 系統(tǒng)防凍

在待機或停機保護期間

? 當環(huán)境溫度≤5℃時,進入一級防凍保護,打開空調(diào)閥,水泵每隔10 分鐘后開啟30 秒,循環(huán)運行;當環(huán)境溫度≥8℃時,退出一級防凍保護;

? 當環(huán)境溫度≤5℃,且出水溫度≤2℃時,進入二級防凍保護,自動開機制熱;? 當環(huán)境溫度≥8℃或出水溫度≥15℃時,退出二級防凍保護;

? 如出水溫度故障時,則由進水溫度代替出水溫度進行防凍;

? 如環(huán)境溫度故障,則進入一級防凍,是否進入二級防凍看出水溫度;? 如環(huán)境、出水、進水溫度都出現(xiàn)故障時,則進入一級防凍;

第13頁

佛山鎧耐空調(diào)設備有限公司建筑冷熱源一體化解決專家 第13頁/共24頁電 氣 控 制 及 安 裝

? 進入防凍后線控器“循環(huán)泵”和“制熱”圖標閃爍;

18) 直流電機保護

? 選擇直流風機時,若連續(xù) 20 秒檢測到直流風機失速或無反饋時,報直流風機故障,停整機;顯示板顯示故障代碼 E64;直流風機關(guān)閉 3 分鐘后自動退出故障,如60 分鐘內(nèi)連續(xù)出現(xiàn)5次,非掉電不可恢復。

2.7 保護代碼查詢

長按 鍵 10s 進入查詢保護代碼界面:

若同時有多個保護,輪流顯示

如沒有保護,顯示- - - -按 鍵,返回主界面

二、電氣安裝

現(xiàn)場需要安裝連線的線路有外接電源線、控制器線、機組連接線以及客戶配置水泵電源線以及控制信號線。在機組安裝到位以后,即可連接電源線電器控制及安裝和連接線,所有導線必須連接牢固,并且不得與任何運動部件接觸。所有連接線必須采用橡膠線(要求采用YZW-300/500、IEC57 號氯丁橡膠線),所有導線必須滿足本手冊要求。機組要求必須有接地措施。所有的電器設備及其安裝工作都必須符合國家及當?shù)匕踩?guī)范的要求,器具應按照國家布線規(guī)則進行安裝。固定線路必須配有至少 3mm 觸點開距的全極斷開裝置。序號 機型型號 線徑規(guī)格(mm2) 配置空氣開關(guān)(A)1 CAR-12 2*6+1*2.5 32

2 CAR-20 2*10+1*2.5 60

3 CAR-24 2*10+1*2.5 60

3 CAR-32 2*10+1*2.5 60

注:圖表所列為機組進線總線線徑;地線應長于其他動力線,以防地線被拉斷。信號線與主電源線必須分開單獨布線。

第14頁

佛山鎧耐空調(diào)設備有限公司第 14頁/共 24頁 建筑冷熱源一體化解決專家

電氣控制及安裝A. 電路圖

電路圖 A

第15頁

佛山鎧耐空調(diào)設備有限公司建筑冷熱源一體化解決專家 第15頁/共24頁電氣控制及安裝電路圖 B

第16頁

佛山鎧耐空調(diào)設備有限公司第 16頁/共 24頁 建筑冷熱源一體化解決專家

機 組 安 裝

只有專業(yè)人員才能進行機組的安裝與調(diào)試!一、安裝準備

驗收

收到貨物時應對機組進行仔細檢查,以確認運輸過程中是否出現(xiàn)貨物破損現(xiàn)象,并按照裝箱單清點主機及附件,

檢查

機組出廠前已充好氟利昂,安裝調(diào)試前注意檢查機組在運輸搬運過程中制冷劑有無泄漏。搬運

搬運時應使用叉車、起重機或吊索,將機組搬運到指定地點,搬運時要采取減震措施,防止碰撞、擦壞機組外部噴涂。機組應保持垂直狀態(tài),嚴禁機組傾斜角度超過30°。起吊時,吊繩不得碰風機及網(wǎng)罩!吊裝時人員不可站于機器下方!

二、機組安裝

1、安裝位置

機組應安裝在室外,且應與鄰近墻面保持適當距離,如圖12 所示,以免阻止空氣流通影響空調(diào)效果,同時也便于檢修。由于冷水機組具有一定的振動及噪音,安裝時要求牢固、可靠,底部應稍微向后傾斜,但傾斜度不大于 5°,這樣有利于冷凝水的排除。本機組可安裝于地面、屋頂、陽臺或其它任何便于安裝并可承受機組運行重量的地方。707400地面 地面400

>200

墻面

側(cè)面圖正面圖圖 6 機組室外安裝圖

第17頁

佛山鎧耐空調(diào)設備有限公司建筑冷熱源一體化解決專家 第17頁/共24頁機組安裝A、可能避免排風方向面對常年強風方向,保證排風不會回流。B、安裝位置要有足夠強度,機組底腳應設減振器或減振墊,減少震動傳遞。C、應避免安裝在臟物、落葉及昆蟲聚集環(huán)境處,以防堵塞換熱器。D、盡可能在機組上方安裝遮陽棚,保護機組。

E、換熱器應定期清掃,確保換熱效率。

F、機組應安裝于離電源、水源較近的地方,以便于配線和補水。G、機組不可使用還含有油、鹽、腐蝕性氣體的環(huán)境中,這些物質(zhì)會對、機組產(chǎn)生腐蝕,引起故障甚至縮短機組壽命。

2、機組基礎

機組可直接用膨脹螺栓固定在機座上,機座安裝定位孔位置見機組外形圖所示,機座可用水泥預制,預留排水溝。也可用槽鋼或工字鋼制作托架、加防震橡膠墊,置于地面或屋頂平面。機座表面應水平

三、水系統(tǒng)安裝

1、循環(huán)式熱水機組配管示意圖

單向閥

Y型過濾器壓力膨脹罐3L單向閥Y型過濾器自來水補水電輔熱系統(tǒng)

電源控

線4m

2熱

線6m

2熱

制箱

總電源線10m

2接用戶電表接室內(nèi)采暖供水管接室內(nèi)采暖回水管旁通閥PPR-32

PPR-32

PPR-20

PPR-20地面

水流開關(guān)截止閥

截止閥

循環(huán)水泵

截止閥截止閥圖7 循環(huán)式熱泵機組接管示意圖

注 意

第18頁

佛山鎧耐空調(diào)設備有限公司第 18頁/共 24頁 建筑冷熱源一體化解決專家

機 組 安 裝

注 意: A、循環(huán)水系統(tǒng)配管完成后,于開機前必須將水系統(tǒng)中空氣排盡;B、水流開關(guān)安裝在水平直管段,距彎頭、閥門等局部阻力件5倍以上管徑C、為提高制冷(制熱)效果和節(jié)約能源,管道需保溫嚴密。

D、機組接管口必須安裝排水管以方便排盡機組內(nèi)水,防止凍結(jié)。E、虛線框內(nèi)的配件為用戶自行配置。

F、在停電或者長時間不開機時,必須將沖洗閥和排水閥打開,排干凈機組及管道中的水。2、設計安裝

有關(guān)室內(nèi)機組及管道系統(tǒng)的設計安裝原則應由專業(yè)人士并參照有關(guān)技術(shù)規(guī)范及技術(shù)要求進行,根據(jù)合適的屋型來設計管路走向,上圖只為客戶安裝提供一個參考。在安裝過程中,要注意幾點:

A、管道布置合理,如右圖所

示,應采取如 A 管路走向而非 B 管路走

向, 盡量減少,彎曲、杜絕“U”形彎、“

門”形彎。避免“U”形彎、以免由此造

成排氣不暢,增大水阻,形成氣塞。

圖 8 水管示意圖B、水管安裝應垂直或水平,管路及連接部位均不得有漏水現(xiàn)象并保溫良好。應在管道的最高處設置排氣閥及補水膨脹水箱(開式水箱)。

C、水平的管道走向要保持一定的坡度(3‰),以便順利將氣體排出。D、冷水系統(tǒng)應參考本說明書所示方法配管,并按照水暖管道標準正確施工。E、應盡可能地減小水循環(huán)系統(tǒng)的阻力損失。

F、水系統(tǒng)與本機組進出水連接口處及水系統(tǒng)的最低點均設置放水口,以便在長時間停止使用時,從兩處放水口同時放出機組及系統(tǒng)內(nèi)的水,防止冬季水在換熱器、水泵及管道內(nèi)凍結(jié),使機組損壞。

G、在進水管中應安裝水過濾器,安裝時注意流向,并在水過濾器兩端加裝截止閥,以便拆卸清洗過濾器。

H、水系統(tǒng)配管完成后,應進行水壓試漏并排污,確保系統(tǒng)內(nèi)清潔,無銹渣污物,管路方可與室外主機連接,以防污物進入機組,使換熱器堵塞,造成機組損壞。AB門形彎U形彎

第19頁

佛山鎧耐空調(diào)設備有限公司建筑冷熱源一體化解決專家 第19頁/共24頁運行調(diào)試一、運行前準備工作

1. 熱泵機組檢查

檢查機組外觀及機內(nèi)管路系統(tǒng)是否在安裝、運輸過程中遭到損害。檢查風機扇葉是否與風扇固定板和風扇護網(wǎng)干涉。

檢查機組壓力表是否仍有壓力,確認制冷劑是否泄漏。

2. 檢查配電系統(tǒng)

檢查所供電電源是否與本說明書和機組銘牌上所要求的供電電源一致。檢查所有供電和控制線路是否全部連接到位,是否按接線圖正確接線,接地是否可靠,所有接線端子是否全部緊固。確認相序正確。

3. 檢查管路系統(tǒng)

檢查系統(tǒng)管路、補水管、回水管、壓力表、溫度計、閥門、水位開關(guān)等設備是否安裝正確。

檢查系統(tǒng)中應該開啟的閥門是否已全部開啟,應該關(guān)閉的閥門是否已全部關(guān)閉。檢查機組水管內(nèi)是否存在空氣,若有,應利用機內(nèi)水管上的手動排氣閥和水泵上的排氣閥,將機組管路內(nèi)的空氣排盡。

檢查系統(tǒng)的保溫措施是否良好。確保水系統(tǒng)過濾器無堵塞現(xiàn)象,使水路暢通無阻。確認水系統(tǒng)已經(jīng)清洗干凈

二、試運行

機組運行必須由專業(yè)人員操作!

當對整個系統(tǒng)進行全面檢查確認符合要求后,可進行整體試運轉(zhuǎn),試運轉(zhuǎn)前,壓縮機須預熱 12 小時。可進行整體試運行。

接通電源,開啟熱泵,主機延時 3 分鐘后自動啟動。對于三相電源機組,首先檢查風扇、水泵轉(zhuǎn)向是否正確,如轉(zhuǎn)向不對立即關(guān)閉電源,調(diào)整相序。測量壓縮機運轉(zhuǎn)電流,有無異常聲音。

觀察水溫變化以及機組的壓力變化有無異常。

檢查機組是否符合要求,運行一段時間后,便可投入正常使用。

第20頁

佛山鎧耐空調(diào)設備有限公司第 20頁/共 24頁 建筑冷熱源一體化解決專家

故 障 代 碼 表

線控器故障保護代碼顯示表

序號 故障原因

故障

代碼

進入條件 解決措施1 主板與驅(qū)動板通訊故障 Er 10 數(shù)據(jù)線及連接問題 檢查數(shù)據(jù)線并連接好主板接收操作板失敗 換新的控制面板2 線控器與主板通訊故障 Er 10 數(shù)據(jù)線及連接問題 檢查數(shù)據(jù)線并連接好主板接收操作板失敗 換新的控制面板4 回水溫度傳感器損壞 Er 15

電路板上感溫探頭未插好或松動重新插好感溫探頭感溫探頭損壞 更換相應感溫探頭5 出水溫度傳感器損壞 Er 27

電路板上感溫探頭未插好或松動重新插好感溫探頭感溫探頭損壞 更換相應感溫探頭6 制冷蒸發(fā)盤管故障傳感

器故障

Er 33

電路板上感溫探頭未插好或松動重新插好感溫探頭感溫探頭損壞 更換相應感溫探頭7 壓縮機回氣溫度傳感器

故障

Er 29

電路板上感溫探頭未插好或松動重新插好感溫探頭感溫探頭損壞 更換相應感溫探頭8 室外盤管溫度傳感器故

Er 16

電路板上感溫探頭未插好或松動重新插好感溫探頭感溫探頭損壞 更換相應感溫探頭9 環(huán)境溫度傳感器損壞 Er 21

電路板上感溫探頭未插好或松動重新插好感溫探頭感溫探頭損壞 更換相應感溫探頭10 排氣溫度傳感器損壞 Er 18

電路板上感溫探頭未插好或松動重新插好感溫探頭感溫探頭損壞 更換相應感溫探頭11 壓縮機 EVI 回氣傳感器

故障

Er 29

電路板上感溫探頭未插好或松動重新插好感溫探頭感溫探頭損壞 更換相應感溫探頭12 內(nèi)環(huán)境溫度傳感器故障 Er 21

電路板上感溫探頭未插好或松動重新插好感溫探頭感溫探頭損壞 更換相應感溫探頭13 壓機高壓故障 Er 05

膨脹閥開度太小 調(diào)大膨脹閥過熱度水流量過小

檢查水管路閥是否完全打開,或更改水泵,加大流量換熱器結(jié)垢

機組運行一段時間后會產(chǎn)生結(jié)垢現(xiàn)象,清洗16 壓機低壓故障 Er 06

膨脹閥開度太小 調(diào)大熱力膨脹閥開度系統(tǒng)有泄漏 檢漏并重新加注冷媒翅片換熱器積塵

機組運行一段時間后會產(chǎn)生積塵現(xiàn)象,清洗17 水流保護 Er 03

水流開關(guān)未正確接入電控箱內(nèi)端子排

正確連接好水流開關(guān)的調(diào)節(jié)彈簧的預緊力調(diào)整不正確,造成雖有足夠水流量但水流開關(guān)不閉合

調(diào)整水流開關(guān)水流開關(guān)安裝不正確(方向錯誤,水流開關(guān)的閥片選擇錯誤)重新安裝水流開關(guān)

第21頁

佛山鎧耐空調(diào)設備有限公司建筑冷熱源一體化解決專家 第21頁/共24頁故障代碼表18 進出水溫差過大保護 Er 15

水流量偏小 調(diào)整水流量系統(tǒng)有堵塞 清理水系統(tǒng)水泵未運行 檢查水泵E20 故障會同時顯示以下故障序號,如壓機輸出缺相顯示: E20 8 。其中 1~128 號故障優(yōu)先顯示,在不出現(xiàn) 1~128 故障時才會顯示 257~384 號故障,若同時出現(xiàn)同等優(yōu)先級兩

個及以上故障則顯示序號累加。例如同時出現(xiàn) 16、32 號故障,則顯示48。故障序號 名稱 描述 處理意見1 IPM 過流 IPM 模塊問題 更換變頻模塊2 壓機同步異常 壓機故障 更換壓機4 預留 -- -- 8 壓機輸出缺相 壓機接線斷線,接觸不良 檢查壓機輸入線路16 DC 母線電壓低 輸入電壓過低、PFC 模塊故障 檢查輸入電壓、更換模塊32 DC 母線電壓高 輸入電壓過高、PFC 模塊故障 更換變頻模塊64 散熱片溫度過高 主機風機故障、風道堵塞 檢查風機,風道128 散熱片溫度故障 扇熱片傳感器短路或者開路故障 更換變頻模塊257 通訊故障 變頻模塊未收到主控發(fā)來命令 檢查主控和變頻模塊的通訊連線258 AC 輸入缺相 輸入缺相(三相模塊有效) 檢查輸入線路260 AC 輸入過流 輸入三相不平衡(三相模塊有效) 檢查輸入三相相電壓264 AC 輸入電壓低 輸入電壓過低 檢查輸入電壓272 高壓故障 壓機高壓故障(預留)

288 IPM 溫度過高 主機風機故障、風道堵塞 檢查風機,風道320 壓機峰值電流過高 壓縮機的線電流過大,驅(qū)動程序和壓機不匹配

更換變頻模塊384 PFC 模塊過溫 PFC 模塊溫度過高 檢測PFC 模塊

第22頁

佛山鎧耐空調(diào)設備有限公司第 22頁/共 24頁 建筑冷熱源一體化解決專家

維 護 保 養(yǎng)

一、電氣

1、本機組應配置專用電源,電源電壓波動范圍為-10%至+10%,應使用自動空氣開關(guān),其額定電流為機組運行電流的 1.5 倍,絕對禁止使用閘刀開關(guān)。

注意:固定線路必須配有至少 3mm 觸點開距的全極斷開裝置2、機組應可靠接地,定期檢查機組的供電電源情況。

3、主機開關(guān)切勿頻繁操作,每小時不應超過四次。電控箱應防止受潮。4、經(jīng)常檢查機組的電源和電氣系統(tǒng)的接線是否牢固,電氣元件是否有動作異常,如有應及時維修和更換。

5、機組安裝前,所需要設定的參數(shù),均已由公司設定完畢,一般情況下,不允許用戶自行修改參數(shù),如果確實需要,請與代理商或本公司技術(shù)服務人員聯(lián)系。二、機組

1、長時停機以后再次開機前,機組必須通電預熱 12 小時后才能開機,短時停機后機組不要斷電,給壓縮機預熱,防止開機損壞壓縮機。機組若長期不使用,務必將機組與管路內(nèi)存水排凈。機組冬季停止制熱運行后,機組自動執(zhí)行防凍功能,所以機組絕對不能斷電。2、始終保持機組周圍有良好的熱交換環(huán)境,熱交換器應定期除塵。3、應設專人維修保養(yǎng),定期檢查機組運行的壓力、溫度情況,檢查機組的管接頭及檢修閥頭有無泄漏,并做好記錄。

三、水系統(tǒng)

1、系統(tǒng)內(nèi)之循環(huán)水應保證水質(zhì)良好,應定期檢查、清洗過濾器,以保證足夠的水流量,保證機組的換熱效果。

2、水系統(tǒng)應配用膨脹水箱(部分機組內(nèi)置),循環(huán)水應保持清潔,如果當?shù)厮|(zhì)不太好,應對補水進行處理,方可進入水系統(tǒng)中。系統(tǒng)內(nèi)最好使用軟水。3、定期檢查系統(tǒng)補水及排氣裝置運行是否正常,以免影響水循環(huán),從而影響機組的制冷、制熱效果和機組的壽命。

4、若停機時間較長,應將機組管路中的水放掉,并切斷電源,套好防護罩。再運行時,開機前對系統(tǒng)進行全面檢查。

5、機組出現(xiàn)故障,用戶無法解決時,請電告本公司在當?shù)氐奶丶s維修部,以便及時派人維修。

第23頁

佛山鎧耐空調(diào)設備有限公司建筑冷熱源一體化解決專家 第23頁/共24頁維護保養(yǎng)6、主機冷凝器清洗,本公司建議采用 50℃-60℃、濃度為 15%的熱磷酸液清洗冷凝器,啟動主機自帶循環(huán)水泵清洗 3 小時,最后用自來水沖洗 3 遍。(管道安裝時建議預留三通接口,用絲堵封住一個接口),以備清洗時接管。禁止用腐蝕性的清洗液清洗冷凝器。7、水箱需在使用一段時間后(一般為 12 個月,具體根據(jù)當?shù)厮|(zhì)而定)需清除水垢。8、常檢查水系統(tǒng)的補水、水箱的安全閥、液位控制器和排氣裝置工作是否正常,以免空氣進入系統(tǒng)造成水循環(huán)量減少,從而影響機組的制熱量和機組運行的可靠性。檢查水泵,水路閥門是否正常工作,水管路及水管接頭是否滲漏。

注意:一旦發(fā)生器具以外的接地系統(tǒng)異常情況時,應立即停止使用熱泵機組。并拔下其電源插頭或斷開與供電電路的一切連接,并與制造廠的維修人員聯(lián)系處理。

第24頁

佛山鎧耐空調(diào)設備有限公司建筑冷熱源一體化解決專家 第24頁/共24頁熱 泵 基 本 原 理

一、熱泵機組的介紹

熱泵作為高效集熱并轉(zhuǎn)移熱能的裝置,可以把消耗的電力變?yōu)? 倍甚至3 倍以上的熱能,實現(xiàn)低溫熱能向高溫熱能的搬運,是當今世界最經(jīng)濟最節(jié)能最安全,最環(huán)保的新一代熱水制造設備。二、熱泵機組及工作原理

在自然界中,水總由高處流向低處,熱量也總是從高溫傳向低溫。但人們可以用水泵把水從低處提升到高處,從而實現(xiàn)水的由低處向高處流動,熱泵同樣可以把熱量從低溫傳遞到高溫。所以熱泵實質(zhì)上是一種熱量提升裝置,熱泵的作用是從周圍環(huán)境中吸取熱量,并把它傳遞給被加熱的對象(溫度較高的物體),其工作原理與制冷機相同,都是按照逆卡諾循環(huán)工作的,所不同的只是工作溫度范圍不一樣。

如圖 12 所示,低環(huán)溫變頻空氣源熱泵機組,主要有翅片式蒸發(fā)器、壓縮機、水冷冷凝器和膨脹閥四部分組成,通過讓工質(zhì)不斷完成蒸發(fā)(吸取蒸發(fā)器中的熱量)→壓縮→冷凝(放出熱量)→節(jié)流→再蒸發(fā)的熱力循環(huán)過程,從而將低溫環(huán)境里的熱量轉(zhuǎn)移到水中,低環(huán)溫變頻空氣源熱泵機組在工作時,與普通的空調(diào)以及熱泵機組一樣 ,在蒸發(fā)器中吸收低溫環(huán)境介質(zhì)中的能量 QA:它本身消耗一部分能量,即壓縮機耗電 QB:通過工質(zhì)循環(huán)系統(tǒng)在冷凝器中時行放熱QC,QC=QA+QB,因此低環(huán)溫變頻空氣源熱泵機組的效率為(QB+ QC)/ QB ,而其他加熱設備的加熱效率都小于 1,因此低環(huán)溫變頻空氣源熱泵機組加熱效率遠大于其他加熱設備的效率,可以看出,采用低環(huán)溫變頻空氣源熱泵機組作為加熱裝置可以節(jié)省能源,同時還降低CO2等污染物的排放量,實現(xiàn)節(jié)能減排的效果。進水出水節(jié)流機構(gòu)

水冷冷凝器壓

圖 12 低環(huán)溫變頻空氣源熱泵機組工作原理圖