目 錄 1. 安全注意事項·······················································································12. 安裝要求 ·····························································································12-1 安裝位置·························································································22-2 安裝方法·························································································32-3 電器配線························································································62-4... [收起]
[展開]
博圖BH-05D橫裝500瓦
粉絲: {{bookData.followerCount}}
文本內(nèi)容
第1頁

蘇州博圖制冷設備有限公司

調

BH-05D 工業(yè)機柜空調說明書

第2頁

目 錄

1. 安全注意事項·······················································································1

2. 安裝要求 ·····························································································1

2-1 安裝位置·························································································2

2-2 安裝方法·························································································3

2-3 電器配線························································································6

2-4 機器排水·························································································6

3. 啟動與運轉···························································································6

3-1 運行前后注意事項···········································································6

3-2 機器操作說明··················································································7

4. 維護與保養(yǎng)·························································································10

4-1 定期清潔·······················································································10

4-2 長時間停用時注意··········································································10

5. 故障排除·····························································································10

附錄一······································································································11

附錄二······································································································11

第3頁

1. 安全注意事項

⑴ 當用戶對本空調器進行各種操作時,請先詳讀本使用手冊,并注意本手冊

中所提到的注意事項,以避免出現(xiàn)意外情況;

⑵ 請勿用濕手操作,以免引起觸電;

⑶ 當需要保養(yǎng)或維護時,請先切斷所有電源以免引起觸電事故;

⑷ 空調器上不易放置任何物品,以免滑落造成人員傷害;

⑸ 當機器在運轉時,請勿將手指或任何物品伸入進、出風口,以避免人員受

傷或機器損壞;

⑹ 本機器露天放置做好密封措施以免雨水進入機體內(nèi),并且也不適宜于安裝

在振動較大或者移動的設備上,當客戶必需安裝在此種條件下時,請務必致

電本公司咨詢;

⑺ 本空調器為工業(yè)用設備,當須用于動植物或食品等方面之特殊用途時,請

致電本公司咨詢;

⑻ 禁止自行改裝、修理、拆卸或者移裝,欲進行上述動作前請先向專業(yè)人員

咨詢,以防意外發(fā)生。

2. 安裝要求

本空調器為側掛式系列,側掛式(圖一),為使機組能在理想的狀況下工作,

在安裝上請注意以下要求:

圖一 側掛式

空調器

回風

(熱)

出風

(冷)

第4頁

2-1 安裝位置

⑴ 空調器需安裝在周圍空氣品質良好的環(huán)境中,請勿放置于有腐蝕性氣體、

可燃性氣體、粉塵類氣體、油污類氣體等品質較差的空氣中;如果確實需要

在粉塵及油污等品質較差的環(huán)境中安裝空調器,則一定要每天做好空調器的

清潔和保養(yǎng)工作。

⑵ 空調器應安裝在通風良好且熱量易于排放的地方,因為空調器運行時會

排出熱量,如果空調器周圍排氣不暢很容易導致其周圍的溫度升高,這將影

響空調器的制冷效果。見圖三,空調器進、排風口離墻面的間距應大于

500mm;

⑶ 空調器周圍請勿放置雜物,以保持空氣暢通流通;

⑷ 本空調器不宜放置于陽光可以直射的地方,避免因陽光照射而吸熱,影

響冷卻效果。

⑸ 請安裝本空調器于周圍溫度在 45℃以下的范圍之內(nèi)高溫系列 55℃以下;

⑹ 本機安裝時請注意上下位置擺放正確,絕對不能倒置安裝,前后左右必

須保持垂直,其傾斜角不大于 5°如圖四所示;

⑺ 控制箱內(nèi)正對出風口的電器元件與出風口的最小距離應大于 200mm,因

距離太近電器元件表面易產(chǎn)生水膜現(xiàn)象,從而導致電器故障的發(fā)生。若無法

避免,請在電器元件前增加一塊隔熱材料;并且箱內(nèi)出風口四周的電器元件

與出風口應保持一定的距離,以便減小箱內(nèi)空氣的流通阻力。

⑻ 當空調器工作時,電控箱四周應該密封,箱門盡量較少打開次數(shù),以便

箱體內(nèi)空氣的溫、濕度能控制在較為理想的狀態(tài)下。

圖三

第5頁

冷氣機

圖 四

錯 誤 正 確 錯 誤 正 確

2-2 安裝方法

⑴ 當機組在搬運、裝卸時,請始終保持設備處于垂直直立狀態(tài),不要將設

備長期放在露天場所;

⑵ 為使空調器的冷卻效果最佳,請將機組直接安裝在電氣柜的外壁上,請

勿采用風管的形式進行送風,如若確實需要采用風管送風,請先咨詢本公司

技術工程師;

⑶ 空調器在安裝之前,請先確認好安裝位置的強度是否能承載機組,以免

造成人員受傷及設備損壞,當安裝在電氣柜門上時,最好該扇箱門能固定不

動,當需要打開時請先確認好加在門上的重量不會使整個電氣柜傾倒;

⑷ 電氣柜上必須開孔,以便使冷風能進入電控箱內(nèi),具體的開口尺寸請參

見圖五;

第6頁

⑸ 箱體開孔時請嚴格參照開口尺寸進行,孔口處的毛刺必須清除,以免劃

傷機組;

⑹ 當長期使用時請注意安裝螺栓是否損壞或脫落,若有而未加處理,將有

可能導致機器掉落而損壞;

⑺具體的安裝方式如下:

第7頁

C. 用升降車安全的把空調器從安裝面安

裝到電控箱上,注意安裝時把電線先從

電線孔伸入到電箱內(nèi),再在電控箱內(nèi)側

螺栓上墊好墊圈,并用螺帽擰緊。

d. 在機組底部出水口連接好排水管,

用抱箍固定好,另一端請引入排水溝

或蓄水桶內(nèi),檢測電源是否與機組匹

配,然后接上電源即可開機使用。(無

冷凝水空調系列無此項)

b. 卸下機組背后安裝螺釘上

的螺帽與墊圈,控制好螺栓

的伸出長度約 15mm

排水管

蓄水桶

螺帽與墊片

進風口

送風口

a.首先在電控柜上開好與

所選空調相對應的安裝孔

機柜開孔

電源線 機柜側面

或門

第8頁

2-3 電器配線:

⑴ 機組安裝好后請先檢查電源電壓值是否保持在容許額定值內(nèi),請避免電壓

值過高或過低,若所提供的電壓在額定值±10%以內(nèi),本機組可正常使用;

經(jīng)常在超過額定電壓值的環(huán)境中使用,將會大大縮短壓縮機和其他電氣設備

及元件的使用壽命,此類損壞不屬于我公司包修范圍,只負責收費維

修。請用戶千萬注意

⑵ 空調的電器箱在機體內(nèi)部,非專業(yè)維修人員請勿打開電器箱進行操作。機

組引出一根電源線,當安裝好后無需另外接線,將插頭插入電控箱內(nèi)的電源

插座即可;

⑶ 在機組的電器回路上請自行安裝斷路器或漏電保護裝置;

⑷ 請準備本機專用電源插座,不要在同一個插座上使用過多電器裝置,否則

容易使電源超出負載,引發(fā)事故。

2-4 機器排水:

本機器自身有除濕功能,當機器運行時,它會慢慢除去電控箱內(nèi)空氣中的部

分水分,這部分水氣就會以液態(tài)的形式排出,排水管就起到排出這部分水的

作用,排水管的連接請注意以下幾點:(無冷凝水空調系列無此水管項目)

⑴ 請先在機器排水口上連接好短接頭,然后把配給的軟管連接上,再用抱箍

緊固好連接處;

⑵ 根據(jù)實際情況排水軟管長度適當即可,過長部分請切除;

⑶ 排水軟管請勿折彎、壓扁、阻塞或出口高于進口,以免排水不暢,從而導

致機器內(nèi)產(chǎn)生淤水嚴重時產(chǎn)生外溢,引起空調器或者電氣柜故障。

3. 啟動與運行

3-1 運行前后注意事項

⑴ 啟動前請先檢查排水管是否已經(jīng)連接到位,電控箱門是否關嚴,若均已到

位即可插上電源開始工作;

⑵ 當在運轉中需重新啟動空調器時,請間隔 3 分鐘以上,倘若頻繁啟動且間

隔時間過短會引起機器損傷;

第9頁

⑶ 當空調器傾斜時請勿開啟,避免漏水、觸電等情況發(fā)生;

⑷ 空調器在出廠時溫度點已經(jīng)設定好為 30℃,若需重新設定時請控制在允

許范圍之內(nèi)設定,以免引起機器運行不正常;如果空調器有加熱功能,出廠

時設置為 5℃

⑸ 當機器有異常噪音或異味(焦臭)等現(xiàn)象出現(xiàn)時,請馬上關閉空調器,并

請專業(yè)人員進行檢查維修。

3-2 機器操作說明

系統(tǒng)參數(shù)設置界面進入:

使用一組密碼進入?yún)?shù)設置狀態(tài)(出廠默認密碼為 1111),按〖P〗鍵

并保持 3 秒鐘,數(shù)碼管顯示『---0』,按〖▼〗鍵循環(huán)選擇密碼當前

位,按〖▲〗鍵設置當前位密碼值, 密碼設置完成后按〖S〗鍵確認。

如果密碼錯誤,顯示『Err』蜂鳴器響三聲后退出參數(shù)設置狀態(tài);如果

密碼輸入正確,蜂鳴器響一聲,進入?yún)?shù)設置狀態(tài),這時數(shù)碼管顯示

『U10』,用〖▲〗或〖▼〗鍵選擇參數(shù)代碼,選定一個參數(shù)后按〖S〗

鍵顯示該參數(shù)的設定值,這時再按〖▲〗或〖▼〗鍵可對參數(shù)進行設

置,設置完成后再按〖S〗鍵,回到顯示參數(shù)代碼狀態(tài)。

·系統(tǒng)參數(shù)設置界面退出:

當參數(shù)設置完成后必須長按〖P〗鍵 3 秒, 系統(tǒng)退出參數(shù)設置狀態(tài),

此次參數(shù)設置被保存。在參數(shù)設置狀態(tài)如果連續(xù) 30 秒內(nèi)無按鍵操作,

系統(tǒng)退出參數(shù)設置狀態(tài),但此次參數(shù)設置無效,控制器仍按原來的參

數(shù)運行;

工作參數(shù)代碼及設置說明如下表所示:

第10頁

顯示屏信號說明

面板數(shù)碼管說明

4 位紅色數(shù)碼管顯示測量溫度值和告警代碼;

圖標 功能 亮 滅 閃爍

壓縮機 啟動 停止 準備制冷,壓縮機正在延

時保護

AUX 電加熱 運行 ---- ----

風機 運行 停止 ----

維修 有故障 無故障 ----

報警 有告警 無報警 ----

通訊 ---- ---- 正在通訊

HACCP

壓縮機強

強制運行 ---- ----

序 號 顯示代碼 說 明

1 “E01” 溫控傳感器故障(短路或斷路)

3 “E02” 蒸發(fā)器傳感器故障(短路或斷路)

3 “E03” 系統(tǒng)缺氟保護

4 “Hi” 高溫告警

5 “Lo” 低溫告警

6 “EE” 數(shù)據(jù)存取錯誤

7 “Err” 密碼輸入錯誤

8 “iA” 外部無源數(shù)字量輸入告警(系統(tǒng)高壓告警)

9 “UnL” 恢復默認出廠密碼“1111”

10 “FrE 蒸發(fā)器凍結保護

第11頁

序號

參數(shù)代

設置功能 設定范圍 說明

出廠設定

01 U00 制冷溫度設定 25~ 40℃ 30

02 U02 溫差 1.0~ 5.0℃ 5

03 U03 高溫報警溫度

-5.0~50℃ 高溫/低溫設定間隔 1℃

50

04 U04 低溫報警溫度 5

05 U05 蒸發(fā)風機溫度設定 0~40℃ 26

06 U06 蒸發(fā)風機溫差 1.0~ 5.0℃ 2

07 U10 溫控探頭校正

-3.0~+3.0

0

08 U11 蒸發(fā)器探頭校正

-3.0~+3.0

0

09 U12 高溫報警失效 0~1 0:禁用;1:啟用 1

10 U13 低溫報警失效 0~1 0:禁用;1:啟用 1

11 U14 系統(tǒng)缺氟失效 0~1 0:禁用;1:啟用 0

12 U21

蒸發(fā)器探頭使能設

0~1 0:禁用;1:啟用 0

13 U22 壓縮機工作模式 0~1

0:自動模式(啟用壓縮

機)

1:禁用模式

0

14 U24 風機工作模式 0~1

0:溫控模式

1:常開模式

0

15 U26 外部輸入告警模式 0~1

0:常閉;

1:常開

1

16 U28 蜂鳴器報警 0~1 0:禁用;1:啟用 1

17 U29

壓縮機開機延時時

1~5 分鐘 3

18 U30

壓縮機最短持續(xù)運

行時間

1~5 分鐘 3

19 U34 RS485 波特率設定 0~3

0:2400bps

1:4800bps

2:9600bps

3:19200bps

3

20 U35 設備地址 1~99 1

21 U99 密碼 0000 ~

9999

---- 1111

22 End 設定結束

第12頁

控制功能說明:

壓縮機控制

◇當測量溫度 ≥【制冷設定溫度】 + 【溫差】,且壓縮機停機時間大于【壓縮機開機延時

時間】,壓縮機開啟;

◇當測量溫度 ≤【設定溫度】,且壓縮機開機時間大于【壓縮機最短持續(xù)運行時間】,壓

縮機關閉;

例如:【制冷設定溫度】為 25 度, 【溫差】為 2 度,則當溫控傳感器檢測溫度高于 27 度

時啟動壓縮機,溫度

低于 25 度時關閉壓縮機,將溫度控制在 25~27 度之間;

◇壓縮機強制啟動:

1.在壓縮機關閉情況下,按住〖▼〗鍵 5 秒不放,可以強制啟動壓縮機。在壓縮機強制啟

動狀態(tài)下,按住〖▼〗鍵 5 秒不放,可以取消強制啟動壓縮機,壓縮機恢復正常運行。

2.壓縮機在強制啟動狀態(tài)下持續(xù)運行 60min 后,壓縮機恢復正常運行。

壓縮機延時保護

◇運行過程中壓縮機停機,必須經(jīng)過【壓縮機開機延時時間】才能再次啟動;

◇運行過程中壓縮機開啟,必須經(jīng)過【壓縮機最短持續(xù)運行時間】才能以實際情況停機;

風機控制: [289]

控制器在運行過程中,風機按照如下規(guī)則運行:

? 如果風機設定為常開,則送風機始終開啟;

? 如果風機設定為溫控則風機根據(jù)溫控傳感器溫度進行控制??刂茥l件如下:

◇當測量溫度 ≥【蒸發(fā)風機設定溫度】 + 【蒸發(fā)風機溫差】,且風機已經(jīng)停機時間大

于 1 分鐘,風機開啟;

◇當測量溫度 ≤【蒸發(fā)風機設定溫度】,且風機開機時間大于 1 分鐘,風機關閉;

例如:【蒸發(fā)風機設定溫度】為 23 度, 【蒸發(fā)風機溫差】為 2 度,則當溫控傳感器檢測溫

度高于 25 度時啟動風機,溫度低于 23 度時關閉風機,將溫度控制在 23~25 度之間;

4.維護與保養(yǎng)

請定期檢查排水管,并確定無堵塞現(xiàn)象,若排水不良易造成空調器漏水。請定期清洗空氣過

濾網(wǎng)和冷凝器。對于機器上安裝的是尼龍濾網(wǎng)的可直接從側面拔出

4-1 定期清潔

本機的濾網(wǎng)材質為尼龍濾網(wǎng),可直接從網(wǎng)罩上面拉出,用洗滌水清洗干凈,

并晾干后按原樣裝回,一般每周需清洗一次;

⑵ 請用中性清洗劑擦拭機體,避免使用硬刷及酸性清洗劑清洗,嚴禁用水沖

洗空調器,以防發(fā)生觸電事故;

4-2 長時間停用時注意

⑴ 請切斷電源,以防意外;

⑵ 清理冷凝器、過濾網(wǎng)及內(nèi)部油污;

⑶ 請對機器采取防塵措施,延長機器使用壽命。

4. 故障排除

第13頁

故障狀況 1 電源接通后,室內(nèi)、室外風機不運轉

可能原因

※保險絲熔斷

※停電或無電源

狀況排除

※更換保險絲

※檢查電源狀況

故障狀況 2 在運行中突然停機,電控箱內(nèi)溫度高于設定點溫度兩度以上

可能原因

※環(huán)境溫度過高,導致壓縮機熱保護

※過濾網(wǎng)堵塞或者冷凝器過臟,導致壓縮機熱保護

狀況排除

※改善周邊環(huán)境,使散熱暢通

※對過濾器及冷凝器進行清洗

故障狀況 3 機器正常運轉,卻不制冷

可能原因

※壓縮機損壞

※制冷系統(tǒng)泄露

※機組蒸發(fā)器大面積結霜

狀況排除

※更換壓縮機,重新抽真空充注制冷劑

※查出泄露處,并重新抽真空加制冷劑

※立即停機,把設定溫度調高到 35℃,十分鐘后重新開機

◇若上述措施均不能排除故障,請致電本公司咨詢!

附錄 1:產(chǎn)品技術參數(shù)

型號:BH-05D

工作電源: 交流 220V ±10% 頻率 50Hz ±4%

運行電流: <1.85A

功 率: 320W

制冷劑: R134a

制冷量: 500W

防護等級:IP54

允許機柜內(nèi)溫度設定范圍:21--38℃(出廠設定 30℃)

允許使用環(huán)境溫度范圍:-25--45℃

循環(huán)風量: 內(nèi)循環(huán):340m 3/h 外循環(huán):440m 3/h

噪音:55dB

第14頁

附錄 2:電氣原理圖

室內(nèi)風機 室外風機 壓縮機

M1 M2 M3

C2 C3

L

N

PE

t℃溫控器

BH-05D 電路圖主回路 控制回路

第15頁

蘇 州 博 圖 制 冷 設 備 有 限 公 司

地址:蘇州市吳江區(qū)太湖新城鎮(zhèn)同安東路 60 號

電話:0512-63172851 0512-63172852

傳真:0512-63102853 郵編:215223

全國統(tǒng)一服務熱線:400-920-7382

網(wǎng)址:www.botuzl.com Email:botu@botuzl.com.

百萬用戶使用云展網(wǎng)進行簡易電子書制作,只要您有文檔,即可一鍵上傳,自動生成鏈接和二維碼(獨立電子書),支持分享到微信和網(wǎng)站!
收藏
轉發(fā)
下載
免費制作
其他案例
更多案例
免費制作
x
{{item.desc}}
下載
{{item.title}}
{{toast}}