BH-05D 工業(yè)機柜空調說明書
蘇州博圖制冷設備有限公司
機
柜
空
調
說
明
書
BH-05D 工業(yè)機柜空調說明書
目 錄
1. 安全注意事項·······················································································1
2. 安裝要求 ·····························································································1
2-1 安裝位置·························································································2
2-2 安裝方法·························································································3
2-3 電器配線························································································6
2-4 機器排水·························································································6
3. 啟動與運轉···························································································6
3-1 運行前后注意事項···········································································6
3-2 機器操作說明··················································································7
4. 維護與保養(yǎng)·························································································10
4-1 定期清潔·······················································································10
4-2 長時間停用時注意··········································································10
5. 故障排除·····························································································10
附錄一······································································································11
附錄二······································································································11
1. 安全注意事項
⑴ 當用戶對本空調器進行各種操作時,請先詳讀本使用手冊,并注意本手冊
中所提到的注意事項,以避免出現(xiàn)意外情況;
⑵ 請勿用濕手操作,以免引起觸電;
⑶ 當需要保養(yǎng)或維護時,請先切斷所有電源以免引起觸電事故;
⑷ 空調器上不易放置任何物品,以免滑落造成人員傷害;
⑸ 當機器在運轉時,請勿將手指或任何物品伸入進、出風口,以避免人員受
傷或機器損壞;
⑹ 本機器露天放置做好密封措施以免雨水進入機體內(nèi),并且也不適宜于安裝
在振動較大或者移動的設備上,當客戶必需安裝在此種條件下時,請務必致
電本公司咨詢;
⑺ 本空調器為工業(yè)用設備,當須用于動植物或食品等方面之特殊用途時,請
致電本公司咨詢;
⑻ 禁止自行改裝、修理、拆卸或者移裝,欲進行上述動作前請先向專業(yè)人員
咨詢,以防意外發(fā)生。
2. 安裝要求
本空調器為側掛式系列,側掛式(圖一),為使機組能在理想的狀況下工作,
在安裝上請注意以下要求:
圖一 側掛式
空調器
電
控
箱
回風
(熱)
出風
(冷)
2-1 安裝位置
⑴ 空調器需安裝在周圍空氣品質良好的環(huán)境中,請勿放置于有腐蝕性氣體、
可燃性氣體、粉塵類氣體、油污類氣體等品質較差的空氣中;如果確實需要
在粉塵及油污等品質較差的環(huán)境中安裝空調器,則一定要每天做好空調器的
清潔和保養(yǎng)工作。
⑵ 空調器應安裝在通風良好且熱量易于排放的地方,因為空調器運行時會
排出熱量,如果空調器周圍排氣不暢很容易導致其周圍的溫度升高,這將影
響空調器的制冷效果。見圖三,空調器進、排風口離墻面的間距應大于
500mm;
⑶ 空調器周圍請勿放置雜物,以保持空氣暢通流通;
⑷ 本空調器不宜放置于陽光可以直射的地方,避免因陽光照射而吸熱,影
響冷卻效果。
⑸ 請安裝本空調器于周圍溫度在 45℃以下的范圍之內(nèi)高溫系列 55℃以下;
⑹ 本機安裝時請注意上下位置擺放正確,絕對不能倒置安裝,前后左右必
須保持垂直,其傾斜角不大于 5°如圖四所示;
⑺ 控制箱內(nèi)正對出風口的電器元件與出風口的最小距離應大于 200mm,因
距離太近電器元件表面易產(chǎn)生水膜現(xiàn)象,從而導致電器故障的發(fā)生。若無法
避免,請在電器元件前增加一塊隔熱材料;并且箱內(nèi)出風口四周的電器元件
與出風口應保持一定的距離,以便減小箱內(nèi)空氣的流通阻力。
⑻ 當空調器工作時,電控箱四周應該密封,箱門盡量較少打開次數(shù),以便
箱體內(nèi)空氣的溫、濕度能控制在較為理想的狀態(tài)下。
圖三
電
控
箱
冷氣機
圖 四
錯 誤 正 確 錯 誤 正 確
2-2 安裝方法
⑴ 當機組在搬運、裝卸時,請始終保持設備處于垂直直立狀態(tài),不要將設
備長期放在露天場所;
⑵ 為使空調器的冷卻效果最佳,請將機組直接安裝在電氣柜的外壁上,請
勿采用風管的形式進行送風,如若確實需要采用風管送風,請先咨詢本公司
技術工程師;
⑶ 空調器在安裝之前,請先確認好安裝位置的強度是否能承載機組,以免
造成人員受傷及設備損壞,當安裝在電氣柜門上時,最好該扇箱門能固定不
動,當需要打開時請先確認好加在門上的重量不會使整個電氣柜傾倒;
⑷ 電氣柜上必須開孔,以便使冷風能進入電控箱內(nèi),具體的開口尺寸請參
見圖五;
⑸ 箱體開孔時請嚴格參照開口尺寸進行,孔口處的毛刺必須清除,以免劃
傷機組;
⑹ 當長期使用時請注意安裝螺栓是否損壞或脫落,若有而未加處理,將有
可能導致機器掉落而損壞;
⑺具體的安裝方式如下:
C. 用升降車安全的把空調器從安裝面安
裝到電控箱上,注意安裝時把電線先從
電線孔伸入到電箱內(nèi),再在電控箱內(nèi)側
螺栓上墊好墊圈,并用螺帽擰緊。
d. 在機組底部出水口連接好排水管,
用抱箍固定好,另一端請引入排水溝
或蓄水桶內(nèi),檢測電源是否與機組匹
配,然后接上電源即可開機使用。(無
冷凝水空調系列無此項)
b. 卸下機組背后安裝螺釘上
的螺帽與墊圈,控制好螺栓
的伸出長度約 15mm
排水管
蓄水桶
螺帽與墊片
進風口
送風口
a.首先在電控柜上開好與
所選空調相對應的安裝孔
電
控
箱
電
控
箱
機柜開孔
電源線 機柜側面
或門
2-3 電器配線:
⑴ 機組安裝好后請先檢查電源電壓值是否保持在容許額定值內(nèi),請避免電壓
值過高或過低,若所提供的電壓在額定值±10%以內(nèi),本機組可正常使用;
經(jīng)常在超過額定電壓值的環(huán)境中使用,將會大大縮短壓縮機和其他電氣設備
及元件的使用壽命,此類損壞不屬于我公司包修范圍,只負責收費維
修。請用戶千萬注意
⑵ 空調的電器箱在機體內(nèi)部,非專業(yè)維修人員請勿打開電器箱進行操作。機
組引出一根電源線,當安裝好后無需另外接線,將插頭插入電控箱內(nèi)的電源
插座即可;
⑶ 在機組的電器回路上請自行安裝斷路器或漏電保護裝置;
⑷ 請準備本機專用電源插座,不要在同一個插座上使用過多電器裝置,否則
容易使電源超出負載,引發(fā)事故。
2-4 機器排水:
本機器自身有除濕功能,當機器運行時,它會慢慢除去電控箱內(nèi)空氣中的部
分水分,這部分水氣就會以液態(tài)的形式排出,排水管就起到排出這部分水的
作用,排水管的連接請注意以下幾點:(無冷凝水空調系列無此水管項目)
⑴ 請先在機器排水口上連接好短接頭,然后把配給的軟管連接上,再用抱箍
緊固好連接處;
⑵ 根據(jù)實際情況排水軟管長度適當即可,過長部分請切除;
⑶ 排水軟管請勿折彎、壓扁、阻塞或出口高于進口,以免排水不暢,從而導
致機器內(nèi)產(chǎn)生淤水嚴重時產(chǎn)生外溢,引起空調器或者電氣柜故障。
3. 啟動與運行
3-1 運行前后注意事項
⑴ 啟動前請先檢查排水管是否已經(jīng)連接到位,電控箱門是否關嚴,若均已到
位即可插上電源開始工作;
⑵ 當在運轉中需重新啟動空調器時,請間隔 3 分鐘以上,倘若頻繁啟動且間
隔時間過短會引起機器損傷;
⑶ 當空調器傾斜時請勿開啟,避免漏水、觸電等情況發(fā)生;
⑷ 空調器在出廠時溫度點已經(jīng)設定好為 30℃,若需重新設定時請控制在允
許范圍之內(nèi)設定,以免引起機器運行不正常;如果空調器有加熱功能,出廠
時設置為 5℃
⑸ 當機器有異常噪音或異味(焦臭)等現(xiàn)象出現(xiàn)時,請馬上關閉空調器,并
請專業(yè)人員進行檢查維修。
3-2 機器操作說明
系統(tǒng)參數(shù)設置界面進入:
使用一組密碼進入?yún)?shù)設置狀態(tài)(出廠默認密碼為 1111),按〖P〗鍵
并保持 3 秒鐘,數(shù)碼管顯示『---0』,按〖▼〗鍵循環(huán)選擇密碼當前
位,按〖▲〗鍵設置當前位密碼值, 密碼設置完成后按〖S〗鍵確認。
如果密碼錯誤,顯示『Err』蜂鳴器響三聲后退出參數(shù)設置狀態(tài);如果
密碼輸入正確,蜂鳴器響一聲,進入?yún)?shù)設置狀態(tài),這時數(shù)碼管顯示
『U10』,用〖▲〗或〖▼〗鍵選擇參數(shù)代碼,選定一個參數(shù)后按〖S〗
鍵顯示該參數(shù)的設定值,這時再按〖▲〗或〖▼〗鍵可對參數(shù)進行設
置,設置完成后再按〖S〗鍵,回到顯示參數(shù)代碼狀態(tài)。
·系統(tǒng)參數(shù)設置界面退出:
當參數(shù)設置完成后必須長按〖P〗鍵 3 秒, 系統(tǒng)退出參數(shù)設置狀態(tài),
此次參數(shù)設置被保存。在參數(shù)設置狀態(tài)如果連續(xù) 30 秒內(nèi)無按鍵操作,
系統(tǒng)退出參數(shù)設置狀態(tài),但此次參數(shù)設置無效,控制器仍按原來的參
數(shù)運行;
工作參數(shù)代碼及設置說明如下表所示:
顯示屏信號說明
面板數(shù)碼管說明
4 位紅色數(shù)碼管顯示測量溫度值和告警代碼;
圖標 功能 亮 滅 閃爍
壓縮機 啟動 停止 準備制冷,壓縮機正在延
時保護
AUX 電加熱 運行 ---- ----
風機 運行 停止 ----
維修 有故障 無故障 ----
報警 有告警 無報警 ----
通訊 ---- ---- 正在通訊
HACCP
壓縮機強
制
強制運行 ---- ----
序 號 顯示代碼 說 明
1 “E01” 溫控傳感器故障(短路或斷路)
3 “E02” 蒸發(fā)器傳感器故障(短路或斷路)
3 “E03” 系統(tǒng)缺氟保護
4 “Hi” 高溫告警
5 “Lo” 低溫告警
6 “EE” 數(shù)據(jù)存取錯誤
7 “Err” 密碼輸入錯誤
8 “iA” 外部無源數(shù)字量輸入告警(系統(tǒng)高壓告警)
9 “UnL” 恢復默認出廠密碼“1111”
10 “FrE 蒸發(fā)器凍結保護
序號
參數(shù)代
碼
設置功能 設定范圍 說明
出廠設定
值
01 U00 制冷溫度設定 25~ 40℃ 30
02 U02 溫差 1.0~ 5.0℃ 5
03 U03 高溫報警溫度
-5.0~50℃ 高溫/低溫設定間隔 1℃
50
04 U04 低溫報警溫度 5
05 U05 蒸發(fā)風機溫度設定 0~40℃ 26
06 U06 蒸發(fā)風機溫差 1.0~ 5.0℃ 2
07 U10 溫控探頭校正
-3.0~+3.0
℃
0
08 U11 蒸發(fā)器探頭校正
-3.0~+3.0
℃
0
09 U12 高溫報警失效 0~1 0:禁用;1:啟用 1
10 U13 低溫報警失效 0~1 0:禁用;1:啟用 1
11 U14 系統(tǒng)缺氟失效 0~1 0:禁用;1:啟用 0
12 U21
蒸發(fā)器探頭使能設
定
0~1 0:禁用;1:啟用 0
13 U22 壓縮機工作模式 0~1
0:自動模式(啟用壓縮
機)
1:禁用模式
0
14 U24 風機工作模式 0~1
0:溫控模式
1:常開模式
0
15 U26 外部輸入告警模式 0~1
0:常閉;
1:常開
1
16 U28 蜂鳴器報警 0~1 0:禁用;1:啟用 1
17 U29
壓縮機開機延時時
間
1~5 分鐘 3
18 U30
壓縮機最短持續(xù)運
行時間
1~5 分鐘 3
19 U34 RS485 波特率設定 0~3
0:2400bps
1:4800bps
2:9600bps
3:19200bps
3
20 U35 設備地址 1~99 1
21 U99 密碼 0000 ~
9999
---- 1111
22 End 設定結束
控制功能說明:
壓縮機控制
◇當測量溫度 ≥【制冷設定溫度】 + 【溫差】,且壓縮機停機時間大于【壓縮機開機延時
時間】,壓縮機開啟;
◇當測量溫度 ≤【設定溫度】,且壓縮機開機時間大于【壓縮機最短持續(xù)運行時間】,壓
縮機關閉;
例如:【制冷設定溫度】為 25 度, 【溫差】為 2 度,則當溫控傳感器檢測溫度高于 27 度
時啟動壓縮機,溫度
低于 25 度時關閉壓縮機,將溫度控制在 25~27 度之間;
◇壓縮機強制啟動:
1.在壓縮機關閉情況下,按住〖▼〗鍵 5 秒不放,可以強制啟動壓縮機。在壓縮機強制啟
動狀態(tài)下,按住〖▼〗鍵 5 秒不放,可以取消強制啟動壓縮機,壓縮機恢復正常運行。
2.壓縮機在強制啟動狀態(tài)下持續(xù)運行 60min 后,壓縮機恢復正常運行。
壓縮機延時保護
◇運行過程中壓縮機停機,必須經(jīng)過【壓縮機開機延時時間】才能再次啟動;
◇運行過程中壓縮機開啟,必須經(jīng)過【壓縮機最短持續(xù)運行時間】才能以實際情況停機;
風機控制: [289]
控制器在運行過程中,風機按照如下規(guī)則運行:
? 如果風機設定為常開,則送風機始終開啟;
? 如果風機設定為溫控則風機根據(jù)溫控傳感器溫度進行控制??刂茥l件如下:
◇當測量溫度 ≥【蒸發(fā)風機設定溫度】 + 【蒸發(fā)風機溫差】,且風機已經(jīng)停機時間大
于 1 分鐘,風機開啟;
◇當測量溫度 ≤【蒸發(fā)風機設定溫度】,且風機開機時間大于 1 分鐘,風機關閉;
例如:【蒸發(fā)風機設定溫度】為 23 度, 【蒸發(fā)風機溫差】為 2 度,則當溫控傳感器檢測溫
度高于 25 度時啟動風機,溫度低于 23 度時關閉風機,將溫度控制在 23~25 度之間;
4.維護與保養(yǎng)
請定期檢查排水管,并確定無堵塞現(xiàn)象,若排水不良易造成空調器漏水。請定期清洗空氣過
濾網(wǎng)和冷凝器。對于機器上安裝的是尼龍濾網(wǎng)的可直接從側面拔出
4-1 定期清潔
本機的濾網(wǎng)材質為尼龍濾網(wǎng),可直接從網(wǎng)罩上面拉出,用洗滌水清洗干凈,
并晾干后按原樣裝回,一般每周需清洗一次;
⑵ 請用中性清洗劑擦拭機體,避免使用硬刷及酸性清洗劑清洗,嚴禁用水沖
洗空調器,以防發(fā)生觸電事故;
4-2 長時間停用時注意
⑴ 請切斷電源,以防意外;
⑵ 清理冷凝器、過濾網(wǎng)及內(nèi)部油污;
⑶ 請對機器采取防塵措施,延長機器使用壽命。
4. 故障排除
故障狀況 1 電源接通后,室內(nèi)、室外風機不運轉
可能原因
※保險絲熔斷
※停電或無電源
狀況排除
※更換保險絲
※檢查電源狀況
故障狀況 2 在運行中突然停機,電控箱內(nèi)溫度高于設定點溫度兩度以上
可能原因
※環(huán)境溫度過高,導致壓縮機熱保護
※過濾網(wǎng)堵塞或者冷凝器過臟,導致壓縮機熱保護
狀況排除
※改善周邊環(huán)境,使散熱暢通
※對過濾器及冷凝器進行清洗
故障狀況 3 機器正常運轉,卻不制冷
可能原因
※壓縮機損壞
※制冷系統(tǒng)泄露
※機組蒸發(fā)器大面積結霜
狀況排除
※更換壓縮機,重新抽真空充注制冷劑
※查出泄露處,并重新抽真空加制冷劑
※立即停機,把設定溫度調高到 35℃,十分鐘后重新開機
◇若上述措施均不能排除故障,請致電本公司咨詢!
附錄 1:產(chǎn)品技術參數(shù)
型號:BH-05D
工作電源: 交流 220V ±10% 頻率 50Hz ±4%
運行電流: <1.85A
功 率: 320W
制冷劑: R134a
制冷量: 500W
防護等級:IP54
允許機柜內(nèi)溫度設定范圍:21--38℃(出廠設定 30℃)
允許使用環(huán)境溫度范圍:-25--45℃
循環(huán)風量: 內(nèi)循環(huán):340m 3/h 外循環(huán):440m 3/h
噪音:55dB
附錄 2:電氣原理圖
室內(nèi)風機 室外風機 壓縮機
M1 M2 M3
C2 C3
L
N
PE
t℃溫控器
BH-05D 電路圖主回路 控制回路
溫
控
器
蘇 州 博 圖 制 冷 設 備 有 限 公 司
地址:蘇州市吳江區(qū)太湖新城鎮(zhèn)同安東路 60 號
電話:0512-63172851 0512-63172852
傳真:0512-63102853 郵編:215223
全國統(tǒng)一服務熱線:400-920-7382